IST5 Tower UPS 10kVA~40kVA User Manual 33
Operations
81
Power Share Fail-Set
Power share is not in balance
82
Power Share Fail-Clear
Incident above disappears
83
Input Volt Detect Fail-Set
Input Voltage is abnormal
84
Input Volt Detect Fail-
Clear
Incident above disappears
85
Battery Volt Detect Fail-
Set
Battery Voltage is abnormal
86
Batt Volt Detect Fail-Clear Incident above disappears
87
Output Volt Fail-Set
Output Voltage is abnormal
88
Output Volt Fail-Clear
Incident above disappears
89
Outlet Temp. Error-Set
Outlet Temperature is abnormal
90
Outlet Temp. Error-Clear
Incident above disappears
91
Input Curr Unbalance-Set
Input current is not balance
92
Input Curr Unbalance-
Clear
Incident above disappears
93
DC Bus Over Volt-Set
DC bus over Voltage
94
DC Bus Over Volt-Clear
Incident above disappears
95
REC Soft Start Fail-Set
Rectifier soft start fails
96
REC Soft Start Fail-Clear
Incident above disappears
97
Relay Connect Fail-Set
Relay in
open circuit
98
Relay Connect Fail-Clear
Incident above disappears
99
Relay Short Circuit-Set
Relay shorted
100
Relay Short Circuit-Clear
Incident above disappears
101
No Inlet Temp. Sensor-Set
The inlet temperature sensor is not connected or
abnormal
102
No Inlet Temp Sensor-
Clear
Incident above disappears
103
No Outlet Temp. Sensor-
Set
The Outlet temperature sensor is not connected or
abnormal
104
No Outlet TmpSensor-
Clear
Incident above disappears
105
Inlet Over Temp.-Set
Inlet over temperature
106
Inlet Over Temp.-Clear
Incident above disappears