Installation
24
UPS 30-300kVA User Manual
+
-
N
N
40 batteries in series
Figure2-7
Battery stringwiring diagram
Danger
The battery terminal voltage is of more than 200Vdc, please follow the safety instructions to avoid
electric shock hazard.
Ensure the positive, negative, neutral electrode is correctly connected from the battery unit
terminals to the breaker and from the breaker to the UPS system.
2.5 Cable Entry
Cables can enter the 60kVA-200kVA cabinet from the bottom,can enter the 250kVA-300kVA
cabinetfrom the top, and can enter the 400kVA-500kVA cabinet both from the top and bottom.
The
cable entry is shown in
Figure2-8.