5 Use and Operation
IST6
Series (200K-600K) Modular UPS
User Manual
102
All rights reserved ©
Allis Electric
Co., Ltd.
5.4.3 Emergency Power Off(EPO)
Single UPS running
Press the EPO button of the UPS or the EPO button of total system, the UPS will shut down and
close all output.
Multi UPS running in parallel
EPO linkage is enabled
Press the EPO button of the UPS or the EPO button of total system, all the paralleled UPS will
shut down and close all output.
EPO linkage is not enabled
Press EPO button of one UPS, the output of this UPS will be closed.
Press the EPO button of total system, all paralleled UPS will be shut down and all output will be
closed.