UPS IST7 Series (60K-200K)
User Manual
3 Installation
45
Avoid any object block the ventilation hole on the front panel and rear panel, which is to keep
good ventilation for the UPS, or, it may rise the inner temperature, even influence the UPS
service time.
Figure3-3
Heat-dissipating
The heat-dissipating of IST7- series UPS is the same. In above figure, we take IST7-60 UPS as an
example to illustrate.
3.2.4 Selection for Input and Output Wires
For the wire sectional area selection of AC input and output wires, please refer to Table3-1 for
corresponding recommended values.
Table3-1
Recommended wire and terminal specification
Model
Item
IST7-
60
IST7-
100
IST7-
120
IST7-
160
IST7-
200
M
ains
input
Mains input current (A)
101
164
196
266
329
Recommended
wire sectional
area (mm
2
)
U/V/W/N
35
×
1
70
×
1
70
×
1
120
×
1 70
×
2
Terminal
DT-35 DT-70 DT-70 DT-120 DT-70