UPS IST7 Series (60K-200K)
User Manual
2 Overview
23
NO.
Dry contact definition
Remarks
13
Inverter abnormal
When the UPS inverter is abnormal, and this dry
contact is ON.
14
Single bypass feedback
When detect single bypass feedback, and this dry
contact is ON.
15
Parallel bypass feedback
When detect parallel bypass feedback, and this dry
contact is ON.
16
UPS power on
When the UPS in power on status, and this dry
contact is ON.
17
Fan abnormal
When the fan of UPS is abnormal, and this dry
contact is ON.
18
UPS alarm
When the UPS alarm, and this dry contact is ON.
Get dry contact function of single bypass feedback and parallel bypass feedback in Table2-7 by
customization.
The dry contact port cannot connect with dangerous signal which may damage device or personal safety,
it should connect to SELV circuit after isolation.
2.4 Optional Accessory
The IST7- series UPS can be equipped with different accessories to meet the needs of different users.
2.4.1 SNMP Card and Its Software
SNMP card(as shown in Figure2-16) is installed in the UPS to realize the UPS remote management.