2 Overview
UPS IST7 Series (60K-200K)
User Manual
30
2.4.4 Battery Temperature Compensation
The battery temperature compensation is used to monitor the battery temperature to realize the battery
charging and discharging temperature compensation.
When the battery temperature compensation function is selected, it will be configured that one
temperature control wire, one temperature control extension cord and one 2Pin green terminal.
Figure2-23
Battery temperature compensation connection
The temperature control wire should be fixed in the higher temperature area of the battery.
2.4.5 Surge Protection Device
If the UPS is installed in a lightning-prone area, it’s should install multiple surge protection facilities
in the wire inlet of mains to ensure that the device is safety running. The UPS can equipped with the
surge protection device of grade-C. The SPD grade-C is optional for the series UPS.
The lightning protection facilities are configured.
2.4.6 Battery Release Control Accessory
When the customer needs to install the battery release, it is necessary to add the corresponding battery
release control accessory. The output voltage of the control accessory is 24VDC, and the voltage can
be turned over through the dry contact control, which meets the supplier requirements of shunt release
and under-voltage release.
The output of the control accessory is 24VDC, so it can only meet the release that the power supply
demand is 24VDC.
2.5 Alarm Function
When the UPS is abnormal, it will send sound & light alarm. The alarm or protection function of the
UPS is as shown in Table2-12.