3 Installation
26
Dimensions (unit: mm)
30kVA
40kVA
10
16
16
25
B
≤24
≤24
≤24
≤29.4
C
4.7±0.3
5.83±0.3
5.83±0.3
7.43±0.3
When the 30kVA-40kVA UPS is set to 31mode, the terminal (as shown in Figure3-3) will be
used, and it size requirements are shown in Table3-8.
Figure3-3
Wiring terminal dimensions
Table3-8
Dimensions limit of wiring terminal
Mode
30kVA-40kVA
Dimensions (unit: mm)
25
35
A
≤12.2
≤15.4
B
≥6.15
≥8.3
C
/
≤8.4
D
≤11.5
≤13.3
The equipped wires by our company are all passed the national standard or UL certification, the quality
is perfect and meets the requirements of safety standard. The cross-section area of the above cables is
only a reference value or users connecting 5 meters long. If the length of the cable exceeds 20 meters,
the cross-section of the wires will be increased accordingly
3.3 Mechanical Installation
The installation for the UPS can be tower-mounting and rack-mounting, user can select
suitable installation way according to actual condition.