A Technical Specifications
70
A
Technical Specifications
Model
Index
10kVA
15kVA
20kVA
30kVA
40kVA
In
p
ut
Input mode
3W+ N+PE(can be set as 1W+ N+PE)
3W+ N+PE
Voltage
range (Vac)
When the input voltage in the range of 176
~
280, the UPS can bear load of 100%
rated power;
When the input voltage in the range of 80-176, the output of the UPS needs to
decrease rated power linearly to use
Frequency
range (Hz)
40~70
Bypass
synchronism
track
range(Hz)
50/60±10%(50/60 self-adaption)
Bypass input
voltage range
(Vac)
208/220/230/240±20% (phase voltage) (default is 220)
Input power
factor
≥0.99
Input THDI
Resistive full load:≤3%; non-linear full load: ≤5%