Figure 5: PCA Series Chiller Specifications
POWER
A0537868
OFF
ON
REFRIGERANT
Mini Chiller
PUMP
ON
COMPRESSOR
ON
Portable Chiller
HIGH
PRESSURE
REFRIGERANT
LOW
PRESSURE
PC Series
Application
Engineering
PUMP
PRESSURE
Optional gauge package
Side cover
handle
Sight glass
To Process
(3/4" NPT)
From Process
(3/4" NPT)
(3/4" NPT)
Drain plug
Power cable entrance,
either side
Optional Casters
20"
26"
34"
Front View
Right Side View
Rear View
13 7/16"
18 7/16"
units only)
No Flow indicator
(for pumpless
NO FLOW
Optional gauge package
Model
Capacity
@ 65°F
LWT 75°F
Ambient
Capacity
@ 50°F
LWT 90°F
Ambient
Nominal
Chilled
Water
Compressor
Pump
Process
Connection
Amp
Draw
230/1/60
Dimensions
(inches)
Operating
Weight
Shipping
Weight
Number (Btuh) (Btuh) (gpm)
(hp)
(inches NPT)
Running
L
W
H
(lbs)
(lbs)
PCA-050
8,100
4,800
1.2
1/2
1
/
3
hp,
1.2 gpm
@ 24 psig
3/4
8A
20
26
34
265
265
PCA-100
14,000
9,550
2.4
1
1
/
3
hp,
2.4 gpm
@ 34 psig
3/4
10A
20
26
34
325
325
PCA-150
25,400
16,000
3.6
1-1/2
1
/
3
hp,
3.6 gpm
@ 24 psig
3/4
12A
20
26
34
345
345
Model
Capacity
@ 18°C
LWT
, 24°C
Ambient
Capacity
@ 10°C
LWT
, 32°C
Ambient
Nominal
Chilled
Water
Compressor
Pump
Process
Connection
Amp
Draw
230/1/60
Dimensions
(cm)
Operating
Weight
Shipping
Weight
Number (watts) (watts) (lpm)
(watts)
(inches NPT)
Running
L
W
H
(kg)
(kg)
PCA-050
2,374
1,407
4.5
373
224 watts,
4.5 lpm
@
207
kPa
3/4
8A
51
66
86
120
120
PCA-100
4,103
2,800
9.0
746
224 watts,
9.0 lpm
@
234
kPa
3/4
10A
51
66
86
147
147
PCA-150
7,444
4,690
13.6
1,118
224 watts,
13.6 lpm
@
207
kPa
3/4
12A
51
66
86
156
156