PS QuarterHorse Series Chillers
Page 13
;
If you want to use straight water, contact Application Engineering’s,
Engineering Department.
;
The 1 gallon (3.8 liter) reservoir is
not
designed to withstand water pressure
above 5 psi (34 kPa).
;
The fill opening and vent line must be vented to the atmosphere for proper
operation.
Properly Venting and Filling the Reservoir Tank
To properly vent and fill the tank:
•
Remove the side panel, then remove the bushing installed on the top of the
tank.
•
Install a pipe nipple and tee to the ¾” coupling on top of the tank.
•
Use one side of the tee for the vent line and the other side for the fill line.
•
Fill the tank.
•
Remove the fittings and re-install the bushing
•
Extend the vent line from the tank to a proper drain.
•
Re-install the side panel.
Figure 3
Ethylene Glycol Curve
Ethylene glycol required
Normal operating range is between 30°F and 70°F
for evaporator freeze protection
Chilled water
operating temperature °F
(set point)
10%
20%
30%
Ethylene
glycol
percent
by
volume
0%
0º
30º
40º
50º
60º
70º
Summary of Contents for QuarterHorse Series 0.25 Portable Chiller PS-025
Page 1: ...PS 025 QuarterHorse Series 0 25 hp Portable Chiller Operation and Installation Manual...
Page 16: ...Page 16 PS QuarterHorse Series Chillers Notes...
Page 17: ...PS 025 QuarterHorse Series 0 25 hp Portable Chiller Operation and Installation Manual...
Page 18: ...Page 18 PS QuarterHorse Series Chillers Notes...
Page 20: ...Page 20 PS QuarterHorse Series Chillers Notes...
Page 22: ...Page 22 PS QuarterHorse Series Chillers Notes...
Page 24: ...Page 24 PS QuarterHorse Series Chillers Service Notes...
Page 25: ...PS QuarterHorse Series Chillers Page 25 Service Notes...