PS QuarterHorse Series Chillers
Page 21
6
Routine Maintenance
6-1 Lubrication
Every three months, grease all fan motors and pump motors that do not have
permanently sealed bearings. Remove grease relief plug (motors only) before adding
grease. Failure to do so may result in dislodging the bearing grease retainer, eventually
causing bearing failure.
Compressors are hermetically sealed; no oiling is required.
6-2 Condenser Maintenance
Dirty condenser heat exchange surfaces reduce system capacity.
Brush or vacuum light dirt accumulations. Avoid bending or damaging the fins. Heavy
soil accumulations on the coil require professional steam cleaning; washing from the
outside only makes matters worse.