User Manual 1-3kVA Rev. 9
- Page 21 of Total 30 -
3. Operation
3.4 Configuration Settings
UPS must be working on Bypass Mode in advance for any setting, because
the setting function can not be available on Normal Mode and Battery
Mode.
`
Output Voltage / Frequency
Step 1. In this screen, press the “Enter” key to proceed to the following steps for output voltage
/ frequency adjustment.
Display 11
– Output Voltage/
Frequency Setting Volt/Freq Set
220 VAC 50 Hz
Step 2. The cursor (
→
) will pop up to indicate the output voltage and frequency newly selected.
Display 11
– Output Voltage/
Frequency Setting Volt/Freq Set
220 VAC 50 Hz
Display 11
– Output Voltage/
Frequency Setting Volt/Freq Set
220 VAC 50 Hz
Step 3. Use “Select-Up” or “Select-Down” keys to adjust the output voltage (220V, 230V, and
240V ). Press the “Enter” key to confirm voltage and then the cursor will move to frequency
selection. The output frequency (50Hz, 50HzP, 60Hz, 60HzP) can be adjusted by the same key
operation.
Step 4. Once the correct voltage is selected, press the “Enter” key again to save the selection.
Display 11
– Output Voltage/
Frequency Setting Volt/Freq Set
Save? NO
There is no output on Bypass Mode if frequency is setting on 50Hz/60Hz, on
the other hand, there is output on Bypass Mode if frequency is setting on
50HzP/60HzP.