3 Installation
UPS IST7 (10KVA-40KVA)
User Manual
24
33 mode
10KVA
15KVA
20KVA
30KVA
40KVA
Mains input neutral wire
(N)
4
6
6
16
16
Bypass input neutral wire
(N)
4
6
6
16
16
Bypass input live wire
(U/V/W)
4
6
6
16
16
Mains output live wire
(U/V/W)
4
6
6
16
16
Mains output neutral wire
(N)
4
6
6
16
16
DC input (+/BATN/-)
10
10
10
2*10
2*10
Grounding wire (PE)
4
6
6
16
16
Recommended cross-sectional area of wire (unit: mm
2
, environment temperature: 25
℃
)
31 mode
10kVA
15KVA
20KVA
30KVA
40KVA
Mains input live wire
(U/V/W)
4
6
6
16
16
Input neutral wire (N)
16
25
25
2*25
2*25
Bypass input live wire (L)
16
25
25
2*25
2*25
Mains output live wire (L)
16
25
25
2*25
2*25
Mains output neutral wire
(N)
16
25
25
2*25
2*25
DC input (+/BATN/-)
10
10
10
2*10
2*10