background image

7-19 

 
f. CONTROL & TEST SETUP 

 
Use “

” or ”

 

to select 

“CONTROL & TEST”

, then press ”

 

to confirm. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1. Use “

” or ”

” to select the desired 

item, then press ”

 

to confirm.

 

O

P

E

Y

&

L

L

K L Y

B A T

E S U L T

E S T

&

L E D

T

B U Z Z E R

2 0 0 8 - 1 0 - 0 2

R O T E C T E D

L OA D

U N

U N I T : # 1 . 1

1 1 : 5 9 : 5 9

B Y P A S S

O N

A U T O

O F F

D A I L Y

WE

T E S T

O

I WE E K L Y

MON T H

D I S A B L E

R

C ON T

B

E

T

T

R

S T

C L R

B A

U T

A

A R G E

S

O

B O

H

C

T

F O R C E

T

A B L E

T

A

B

S

E

T

MA NU A L

E N

B U Z Z E R

T E S T

O

P

E

Y

&

L

L

K L Y

B A T

E S U L T

E S T

&

L E D

T

B U Z Z E R

2 0 0 8 - 1 0 - 0 2

R O T E C T E D

L OA D

U N

U N I T : # 1 . 1

1 1 : 5 9 : 5 9

B Y P A S S

O N

A U T O

O F F

D A I L Y

WE

T E S T

O

I WE E K L Y

MON T H

D I S A B L E

R

C ON T

B

E

T

T

R

S T

C L R

B A

U T

A

A R G E

S

O

B O

H

C

T

F O R C E

T

A B L E

T

A

B

S

E

T

MA NU A L

E N

B U Z Z E R

T E S T

O

P

E

Y

&

L

L

K L Y

B A T

E S U L T

E S T

&

L E D

T

B U Z Z E R

2 0 0 8 - 1 0 - 0 2

R O T E C T E D

L OA D

U N

U N I T : # 1 . 1

1 1 : 5 9 : 5 9

B Y P A S S

O N

A U T O

O F F

D A I L Y

WE

T E S T

O

I WE E K L Y

MON T H

D I S A B L E

R

C ON T

B

E

T

T

R

S T

C L R

B A

U T

A

A R G E

S

O

B O

H

C

T

F O R C E

T

A B L E

T

A

B

S

E

T

MA NU A L

E N

B U Z Z E R

T E S T

O

P

E

Y

&

L

L

K L Y

B A T

E S U L T

E S T

&

L E D

T

B U Z Z E R

2 0 0 8 - 1 0 - 0 2

R O T E C T E D

L OA D

U N

U N I T : # 1 . 1

1 1 : 5 9 : 5 9

B Y P A S S

O N

A U T O

O F F

D A I L Y

WE

T E S T

O

I WE E K L Y

MON T H

D I S A B L E

O K ?

R

C ON T

B

E

T

T

R

S T

C L R

B A

U T

A

A R G E

S

O

B O

H

C

T

F O R C E

T

A B L E

T

A

B

S

E

T

MA NU A L

E N

B U Z Z E R

T E S T

2. Battery Auto Test 

Use “

” or ”

” to select     

the desired item, then press ”

 

to 

confirm. If you start a battery test 
once it will be performed at the same 
time of the day due to the timely 
sequence you have chosen with this 
setting.

 

3. Buzzer 

Use “

” or ”

” to select enable or 

disable the buzzer, then press ”

 

to confirm.

 

4. Manual Battery Test 

Press ”

 

to execute 

“MANUAL 

BAT TEST”

 

(This item is only accessible for 
administrator! The Password will be 
needed.)

 

 

Summary of Contents for 80 / 120 kVA

Page 1: ...Uninterruptible Power Supply UPS Protect 3 M 2 0 80 120 kVA Model AEG Power Solutions GmbH Department EMS PM Name Schulz Revision 07 Date 08 09 2011 Operating Instructions 8000029390 BAL en ...

Page 2: ...p Mode Parallel 2 4 2 7 Reserve Bypass Mode Parallel 2 5 2 8 Manual Bypass Mode Parallel 2 6 3 General View 3 1 3 1 Appearance 3 1 3 1 1 Dimensions 80kVA 3 2 3 1 2 Dimensions 120kVA 3 3 3 2 Function Introduction 3 5 3 2 1 Front Panel 3 5 3 2 2 Rear Panel 3 6 3 2 3 External Battery Cabinet Rear Panel 3 7 3 2 4 Power Module 3 9 3 3 Interface 3 10 3 3 1 Dry Contact Input 3 10 3 3 2 Dry Contact Output...

Page 3: ...4 8 4 6 1 Preparations 4 8 4 6 2 Wiring Single Unit 4 10 4 6 3 Connecting External Battery Cabinet 4 12 4 6 4 Wiring Parallel Redundancy Single Input 4 13 4 6 5 Wiring Parallel Redundancy Dual Input 4 14 5 Operating Procedure 5 1 5 1 Startup Procedure Single 5 1 5 2 Battery Startup Procedures Single 5 2 5 3 Shutdown Procedure Single 5 2 5 4 Manual Bypass Startup Single 5 3 5 5 Startup Procedure Pa...

Page 4: ...rarchy 7 2 7 3 Default Screen 7 3 7 3 1 Status Display 7 4 7 4 Main Menu 7 9 7 5 UPS Setup 7 11 a Bypass Setup 7 12 b Output Setup 7 13 c Battery Setup 7 15 d Charger Setup 7 17 e Parallel Setup 7 18 f Control Test Setup 7 19 g Local Setup 7 21 7 6 Maintenance 7 23 ...

Page 5: ...ce is to be done on the UPS Isolate Uninterruptible Power Supply UPS before working on the circuit A readily accessible disconnect device 450V 150A for 80kVA and 225A for 120kVA model shall be incorporated in the fixed wiring HIGH LEAKAGE CURRENT Earth connection essential before connecting power source It is recommended to use a four pole breaker device and which disconnects all line conductors a...

Page 6: ...es are subject to the general conditions of supply for products of the electrical industry and our general sales conditions We reserve the right to alter any specifications given in these operating instructions especially with regard to technical data operation weights and dimensions Claims in connection with supplied goods must be submitted within one week of receipt along with the packing slip S...

Page 7: ...abinet N x parallel redundancy and expansion Up to 4 6 units No need any extra parallel control card High input power factor pf 0 99 and low input current THDI 5 for installation cost savings and utility pollution reduction Overall high efficiency up to 94 5 with modular structure and hot swappable function for operation cost savings Dual input separated rectifier and bypass input Built in manual ...

Page 8: ...able and clean AC power for various loads The Double Conversion technology allows regulating the utility to provide pure and stable power to your precious equipment Refer to Fig 2 1 2 2 Backup Mode Single Installation Fig 2 2 Backup Mode Single When a power event blackout transient surge fluctuation occurs the UPS will automatically transfer from normal mode to backup mode The battery will provide...

Page 9: ...to make sure the supply to the loads After abnormal situations are eliminated UPS will transfer back to the normal mode immediately Refer to Fig 2 3 2 4 Manual Bypass Mode Single Installation Fig 2 4 Manual Bypass Mode Single In maintenance or repair service condition you will need to cut off the UPS power but not the power to your equipment Make sure the UPS is in Bypass mode see LED at the front...

Page 10: ...el Under this installation the load is shared by two UPS units If there is any problem in one of them the load will be entirely handled by the other In case the load is greater than one UPS can take the UPS will shut down and then transfer all UPS to the reserve mode Refer to Fig 2 5 CB1 CB2 CB3 CB4 CB5 UPS1 MAIN RESERVE STS CB1 CB2 CB3 CB4 CB5 LOAD MAIN RESERVE STS UPS2 ...

Page 11: ...ckup Mode Parallel Fig 2 6 Backup Mode Parallel The load is shared by two UPS units when a blackout occurs Refer to Fig 2 6 CB1 CB2 CB3 CB4 CB5 UPS1 MAIN RESERVE STS CB1 CB2 CB3 CB4 CB5 LOAD MAIN RESERVE STS UPS2 ...

Page 12: ... Bypass Mode Parallel The same as what mentioned in Section 2 3 except two UPS units sharing the load All parallel UPS will switch at the same time Refer to Fig 2 7 CB1 CB2 CB3 CB4 CB5 UPS1 MAIN RESERVE STS CB1 CB2 CB3 CB4 CB5 LOAD MAIN RESERVE STS UPS2 ...

Page 13: ...ntioned in Section 2 4 except two UPS units sharing the load Remember that all parallel UPS should be transfer to manual bypass mode The Reserve mains should be equal for all parallel UPS Refer to Fig 2 8 CB1 CB2 CB3 CB4 CB5 UPS1 MAIN RESERVE STS CB1 CB2 CB3 CB4 CB5 LOAD MAIN RESERVE STS UPS2 ...

Page 14: ...3 1 3 General View 3 1 Appearance LCD Display and Control Panel ...

Page 15: ...3 2 3 1 1 Dimensions 80kVA Fig 3 1 Power Unit 80kVA Fig 3 2 External Battery Pack 80 kVA cabinet size ...

Page 16: ...3 3 3 1 2 Dimensions 120kVA Fig 3 3 Power Unit 120 kVA Fig 3 4 External Battery Pack 120 kVA cabinet size ...

Page 17: ...sily removed for maintenance The minimum capacity of each power module is 20KVA and the height is 3U 132cm The capacity can be expanded at most 4 6 modules i e the maximum capacity in a single cabinet is 80KVA 120kVA Hot swap function for module replacement 3 Input and Output Circuit Breakers There are four circuit breakers Input Bypass Manual Bypass and Output LCD Display Control Panel Status LED...

Page 18: ...e internal wiring for power modules 3 Wiring terminal block Remove the cover to perform wiring for input output and external battery Input power source 3 phases L1 L2 L3 and neutral N Bypass input source 3 Phases L1 L2 and L3 External battery pack positive negative and neutral N UPS output 3 Phases L1 L2 L3 and neutral N Protection Earth Interface Wiring Terminal Block Caster Stop Power Modules Fi...

Page 19: ...nce supporter for safety 3 2 3 External Battery Cabinet Rear Panel 1 Monitoring Contacts There are two kinds of messages that can be transmitted Battery cabinet temperature Battery cabinet status For more details refer to Seciton 3 3 2 Protector Protection and control switch for batteries 3 Caster Stop Move the UPS for short distance Casters with stop function Adjustable leveler for stabilization ...

Page 20: ...nnecting the UPS and the next battery cabinet Circuit Breaker Caster Stop Wiring Terminal Block Monitorting Contacts Fig 3 6 Rear View of Battery Cabinet 1165mm height N N Note For longer autonomy times you can connect up to 4 battery cabinets in parallel If you use only one battery cabinet the maximum UPS power for one 1165 mm cabinet is 40kVA for one 1665mm is 60kVA ...

Page 21: ...cted rectifier a battery charger and an inverter with associated monitoring and control circuitry Fail On Off Status LED Locking Latch Fig 3 7 Front View of Power Module Fig 3 8 Rear View of Power Module Fig 3 9 Top View of Power Module CAUTIONS Power Modules are heavy 30kg Two people are required for handling ...

Page 22: ...nt method for users remotely power off the UPS if an emergency event occurs Simply connect the cable from remote site to this terminal The user may install a button or switch to easily press the button to power off the UPS Inverter This REPO is a normal open contact After reopening the REPO contact the inverter will not start automatically 1 2 12V 1 2 4 3 Fig 3 11 REPO Circuit Fig 3 10 Interface R...

Page 23: ...pen type 3 P3 P6 External Battery Cabinet Temperature You can order the optional accessory sensor kit to detect the temperature of external battery cabinet 6000008725 4 P7 Status of External Battery Cabinet Pin1 12V Pin2 The detection cable is connected Pin3 Status of external battery cabinet breaker Signal active means the breaker is on Signal inactive means the breaker is off Pin4 Reserved Pin5 ...

Page 24: ...ry Contact Output 3 4 1 2 12VS DRY1 3 4 1 2 12VS DRY2 3 4 1 2 12VS DRY3 3 4 1 2 12VS DRY4 3 4 1 2 12VS DRY5 3 4 1 2 12VS DRY6 1 2 3 4 5 6 7 8 9 10 11 12 COMM_A COMM_B DRYA_NO DRYB_NO COMM_C COMM_D DRYC_NO DRYC_NO DRYE_NO DRYF_NO COMM_E COMM_F ...

Page 25: ...ning shutdown The temperature is too high 15 Output voltage abnormal The output voltage is too high or too low 16 Battery need replace Overdue for battery replacement Compared with system setup 17 Bypass over temperature warning shutdown Bypass static transfer switch is over temperature 18 Battery ground fault Grounding error 19 Bypass static switch fault The bypass static transfer switch is abnor...

Page 26: ...ny powerful smart cards for various applications There are 4 accessories available as below Please contact your local dealer or agent for orders Smartcard Part No SNMP Adapter PRO 6000001271 SNMP Adapter 6000004036 Relais I O Card 6000008721 MODBUS Card 6000008722 1 6 2 7 3 8 4 9 5 TX RX Fig 3 14 RS232 Use the parallel communication cable in the accessory pack Linking the UPS with other cables mig...

Page 27: ... UPS standard MIB Embedded Web Server Monitoring via Web Configuration via Web Embedded Event Manager Start of different Jobs Net Broadcast E Mail Monitoring of environmental conditions Temperature Humidity GenSet Fire Air condition Smoke shutter Support Software products Network Management Software NMS NMS special for Power Supply Systems Shutdown Software CompuWatch Direct multi server shutdown ...

Page 28: ... C Humidity 10 80 rel Operation Voltage 12 V DC Dimensions D x W x H 130 x 60 x15 mm Weight 66 g SNMP Adapter Part No 6000004036 Same features as SNMP Adapter but only including RJ 45 Network plug in connector No connection of additional dry contacts or external sensors possible ...

Page 29: ...own or Battery Test Configuration over RS 232 terminal server Output contact rating 24VDC 1A Input rating 24V 10mA Technical Specification Relay I O Input Power 8 20VDC Temperature 0 40 C Humidity 10 80 Power Consumption 1 2 Watt Maximum Dimension L x W 130x60mm Weight 200g Maximum DC Voltage DC Current R1 R6 24V 1A Opto Input 24V 10mA ...

Page 30: ...5 Overload R6 Over Temperature Input Remote shutdown or battery test Tx Transmit to PC connect to RS232 pin 2 Rx Receive from PC connect to RS232 pin 3 GND C Ground for configuration connect to RS232 pin 5 OFF Default ON SW1 Normally Open Normally Close SW2 Default Settings Customized Settings Fig 3 15 Circuit diagram Relay I O Card contacts ...

Page 31: ... to install Baud rate and parity options are also adjustable by using dip switches 2 LEDs for indicating communication status Technical Specification I O Definition Input Power 8 20VDC Temperature 0 40 C Humidity 10 80 Power Consumption 1 Watt Maximum Dimension L x W 130x60mm Weight 150g GND Ground for RS232 RS232 Tx Tx to PC RS232 Rx Rx from PC RS422 T RS422 D T for RS422 or D for RS485 RS422 T R...

Page 32: ...ailable in the measuring values which can be displayed see also Page 7 10 Measurements Therefore you have to add the option Battery Current Measurement Part Nr 6000008724 It consists of 2 transducers which have to be placed inside the UPS Note If the option is not installed the UPS display will just show the charging current ...

Page 33: ...ormal Bypass Backup and Fault Display LCD Input Output Bypass Inverter Frequency Loading and Battery voltage current UPS abnormal message and intelligent self diagnosis 6 Integrated Dry contacts Remote 2 integrated Opto inputs Standard RS232 Dry Contact Output Interface Optional SNMP card Modbus card Relay I O control card Environmental sensor Parallel Operation Yes up to 4 UPS of the same type 80...

Page 34: ...examine the UPS or battery pack cabinet 2 Check the rating label on the rear side of cabinet Confirm if the model name and capacity correctly match your original requirements 3 Examine if the parts are loose or damaged 4 Examine any accessory is missing The Protect 3 M 20 Series has the following accessory RS232 cable 1 pcs Length 1 8m Parallel communication cable 1 pcs Length 2m Remote EPO wiring...

Page 35: ... Charging procedures Connect UPS to the utility power If there is an external battery pack connect the cable of battery pack to the UPS The UPS starts up normally At this time the UPS will charge the batteries by internal charging circuit 3 The carton and the original packaging must remain sealed to prevent any possible damage from mouse or similar creatures Connect and power the loading only when...

Page 36: ...4 3 4 4 Unpacking Procedures 4 4 1 Protect 3 M 2 0 80 kVA ...

Page 37: ...4 4 4 4 2 Protect 3 M 2 0 120 kVA ...

Page 38: ...ccident 3 Push the UPS from either front or rear side otherwise could cause tip over accident 4 When the UPS needs a long distance movement make use of a suitable machine but not casters of the UPS 4 5 2 UPS Positioning 1 Position the UPS or external battery pack by suitable machine 2 Refer to Table 4 1 to 4 4 Ensure that the UPS is positioned at a suitable floor which can sustain for the weight 3...

Page 39: ...ery Pack 80 kVA cabinet size Batteries 40 pcs Capacity Ah 12V 26AH Weight kg 487 5 Floor Loading kg 1064 Table 4 3 Floor Loading for 120 kVA UPS Input 230 400 Vac Output 230 400 Vac Capacity KVA 120 Weight Kg 384 Floor Loading kg 748 Table 4 4 Floor Loading for External Battery Pack 120 kVA cabinet size Batteries 40 pcs Capacity Ah 12V 40AH Weight kg 727 Floor Loading kg 1575 ...

Page 40: ...of UPS should be provided to permit free passage of service engineer and ventilation purpose 2 A clearance of at least 50cm between rear bezel of UPS and wall should be provided to permit free passage of service engineer and ventilation purpose 3 A clearance of at least 50cm between the top of UPS and the ceiling should be provided to permit free passage of service engineer 4 A clearance of at lea...

Page 41: ...are ducted very close together it is recommended to use cables with isolations made for higher temperature ranges Table 4 3 Input Output Electrical Data Recommended cross section following DIN EN 60269 1 single wire cables in free air Please consider possible deviation due to installed region 7 Confirm the power phase of L1 L2 and L3 8 Confirm the polarity of battery cable 9 Connect the ground of ...

Page 42: ...oose a cross section according to the maximum UPS power per cabinet For example use for an 80 kVA cabinet always 50mm even if the UPS is not scaled to the max Power now Inside the UPS all Neutrals are connected to one common point Please we aware that all to the UPS connected neutrals are also connected in your external power supply environment ...

Page 43: ...Input neutral terminal Output L1 L2 L3 and neutral External Battery positive negative and neutral Grounding Terminal Protection 3 The rated voltage of standard model is 220 380VAC 230 400VAC or 240 415VAC 4 The battery rating voltage is 240VDC 5 Confirm if the input and bypass input circuit breakers Q1 and Q2 are cut off Refer to Fig 4 2 Remove Cover Main AC Input Bypass Input External Battery Out...

Page 44: ... off 8 According to UPS model you have selected use suitable cables and lugs Refer to Table 4 3 9 Connect all cables to the right terminal or location as indicated Refer to Fig 4 1 Q4 Q3 Q2 Q1 Q1 Input Circuit Breaker Q2 Bypass Input Circuit Breaker Q3 Manual Bypass Switch Q4 Output Circuit Breaker Fig 4 2 Circuit Breaker ...

Page 45: ...6 3 Connecting External Battery Cabinet Connect corresponding terminals N between UPS and external battery cabinet UPS Battery Cabinet Fig 4 3 Wiring of External Battery Cabinet N 240VDC 240VDC N 240VDC 240VDC ...

Page 46: ... Connect the parallel communication cable between UPS1 and UPS2 Refer Fig 4 4 Fig 4 4 Wiring Parallel Redundancy Single Input 1 For installation of parallel system the total cable length of input must be equal to the one of output This regulation prevents unbalanced load shared by two UPSs under reserve mode i e Res1 OP1 Res2 OP2 The deviation must be less than 10 2 Two UPSs must have the same rat...

Page 47: ...Connect the parallel communication cable between UPS1 and UPS2 Refer Fig 4 5 1 For installation of parallel system the total cable length of input must be equal to one of output This regulation prevents unbalanced load shared by two UPSs under reserve mode i e Res1 OP1 Res2 OP2 Deviation must be less than 10 2 Two UPSs must have the same rating capacity 80 or 120kVA for parallel installation Diffe...

Page 48: ...e breaker or fuse of the external battery cabinet Confirm if the locking latch is located at Confirm if there is no voltage potential between NEUTRAL and Ground Confirm if the input power source matches the rated voltage frequency phase and battery of the UPS that you have installed Q4 Q3 Q2 Q1 Fail On Off Q1 Input Circuit Breaker Q2 Bypass Input Circuit Breaker Q3 Manual Bypass Switch Q4 Output C...

Page 49: ...Startup Procedures Single Unit 1 Switch the circuit breaker of external battery cabinet to ON and confirm if Q3 is cut off and switched to OFF 2 Press the I button for 3 seconds until you hear a beep and then release the button 3 The UPS will start up by DC bus soft start The inverter will be activated by adopting the default frequency value 4 When the inverter startup is completed the UPS will tr...

Page 50: ...on Q3 under normal condition the inverter will shut down and the output will be supplied by manual bypass source 2 Manual bypass mode ensures that the UPS supplies the loads from manual bypass source The service personnel can perform maintenance process under this mode without interrupting the load At this moment the UPS is still supplied by input power source If the service personnel want to repl...

Page 51: ...on circuit breaker Q2 of each UPS The LCD screen will show ON AUTO BYPASS 4 Switch on Q1 of each UPS 5 Press the I button for 3 seconds until you hear a beep and then release the button The inverter will be activated and synchronize with bypass source 6 Repeat Step 5 to start up another UPS When the inverter voltage of both UPSs activates normally both UPSs will transfer to normal mode at the same...

Page 52: ...t you want to shut down 3 Switch off Q2 of the UPS that you want to shut down 4 When all the power modules complete the discharging procedures the LCD screen will be off 5 Switch off the battery circuit breaker of the external battery cabinet ...

Page 53: ...upplies the loads The LCD screen shows ON MANUAL BYPASS 6 Switch off Q4 and Q2 of both UPSs The LCD screen will be off 7 Switch off battery circuit breaker of the external battery cabinet 8 In this mode only Q4 and terminal block has hazard voltage Service personnel can perform maintenance work 1 Only for maintenance purpose you can manually turn on the bypass switch If you switch on Q3 under norm...

Page 54: ...f both UPSs Switch off Q3 of both UPSs The LCD screens of both UPSs show ON AUTO BYPASS 3 Switch on Q1 of both UPSs 4 Press the I button for 3 seconds until you hear a beep and then release the button 5 Repeat Step 5 to start up another UPS When the inverter voltage of both UPSs activates normally both UPSs will transfer to normal mode at the same time ...

Page 55: ...is located at the power module is inactive When the locking latch is located at and the main power is turned on the power module is failed FLASHING The power module is failed and had shut down ON The power module is active Note While releasing the locking latch of power module during normal mode the power module is off line but may discharge the DC bus by it s standby current Fail On Off Fail On O...

Page 56: ...t and then move the locking latch to located at 3 Use the screwdriver to unscrew the screws on both sides of power module 4 Two people stand on both sides of the UPS then pull out and lift the power module Reverse procedure for installation of replacement power module WARNING Only trained persons familiar with the construction and operation of the equipment as well as the electrical and mechanical...

Page 57: ...6 3 Fail On Off Fail On Off ...

Page 58: ...when any fault occurs 5 LCD Display Multi language display English German French Italian Spanish Portuguese Turkish Russian and Chinese 6 ESC Page up 7 8 Configuration and Cursor up or down Confirm settings 9 ON Press for 3 seconds to start up the UPS Inverter On 10 OFF Press for 3 seconds to power off the UPS Inverter Off 11 EPO Emergency Power Off Press EPO will power off the inverter immediatel...

Page 59: ...7 2 7 2 LCD Display Protect 3 M 2 0 Series UPS features a user friendly LCD screen to show messages 7 2 1 LCD Display Hierarchy Fig 7 2 LCD Display Hierarchy ...

Page 60: ...ll show as below 1 When any event occurs you will see the sign flashes You can press to see the details For example Press again will go to the next message If there is no further message the screen will return to the default screen 2 Press ESC at any time will return to the default screen ...

Page 61: ...ts off the output Possible causes The UPS automatically shuts down by itself because of an internal error Manually switch off the output circuit breaker 2 This message means the loads are supplied by bypass source due to initial startup of the UPS T 2 0 0 8 1 0 0 2 P OWE R ED LOAD NO UN I T 1 1 1 1 5 9 5 9 R P TO BROWS E EVENT 0 0 4 S E S BYPA MAINS ...

Page 62: ...his message means the UPS is in bypass mode In the mean time the main power source and battery are cut off So the loads may lose power if the bypass source may fail also A 2 0 0 8 1 0 0 2 GNO S I S S E L F D I UN I T 1 1 1 1 5 9 5 9 R P TO BROWS E EVENT 0 0 4 S E S BYPA MAINS ...

Page 63: ...is message means the UPS is in battery backup mode The loads are supplied by battery power 2 0 0 8 1 0 0 2 LOAD UN I T 1 1 1 1 5 9 5 9 ON L I NE P ROT E C T ED BYPA MAINS 2 0 0 8 1 0 0 2 LOAD UN I T 1 1 1 1 5 9 5 9 RY ON BAT T E P ROT E C T ED R P TO BROWS E EVENT 0 0 4 S E S BYPA MAINS ...

Page 64: ... 8 This message means the UPS is in ECO Economic Operation mode The loads are supplied by bypass source 2 0 0 8 1 0 0 2 LOAD UN I T 1 1 1 1 5 9 5 9 BAT T E S T P ROT E C T ED BYPA MAINS 2 0 0 8 1 0 0 2 LOAD UN I T 1 1 1 1 5 9 5 9 ON E CO P ROT E C T ED BYPA MAINS ...

Page 65: ...ce work the UPS must transfer to this mode first In the mean time the main power source and battery are cut off So the loads may lose the power if the bypass source suddenly fails 2 0 0 8 1 0 0 2 LOAD UN UN I T 1 1 1 1 5 9 5 9 L BY P A S S ON MANUA R P TO BROWS E EVENT 0 0 4 S E S BYPA MAINS P ROT E C T ED ...

Page 66: ...ult screen will change to the main menu Press or to select the desired item then press to confirm UR P MA I N E MEA S U P S 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUTO NT ROL TU P CO S E NANC E T E ...

Page 67: ... 0 2 L 1 N N L 2 L 3 N 0 E R P 0 2 0 1 F R E 0 I NVE R T 0 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 2 1 0 2 9 BY P A S S ON AUT O 0 0 H z 6 Q 0 0 6 0 0 6 0 0 6 0 6 6 0 6 0 6 3 4 0 0 0 0 0 0 6 6 0 6 0 6 L 1 L 2 L 3 F R E H z Q F R E H z Q F R E H z Q 0 P 0 V l i 2 V p h a s e 1 OUT P UT 6 3 1 3 2 0 6 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 2 1 0 2 9 BY P A S S ON AUT O L 1 0 7 2 ...

Page 68: ...eter but not to configure 2 The password consists of 4 digitals Use or to select the first number then press for the next digital After all digitals are selected press to confirm the selection Default password is 0000 3 If the password is wrong press to reselect P 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 0 0 0 0 0 0 0 N LOG I 0 I I S R N M AD T RATO R E U S S...

Page 69: ...e UPS SETUP menu S P F R EQ E T U P VOL T 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O V 1 5 ANGE 2 2 0 R z 5 0 5 0 H S S BY P A ANGE R S P F R EQ E T U P VOL T 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O V 1 5 ANGE 2 2 0 R z 5 0 5 0 H S S BY P A ANGE R S P F R EQ E T U P VOL T 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 ...

Page 70: ...in this segment can only be changed under Bypass Mode S P F R EQ E T U P VOL T 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 2 2 0 0 6 0 ON O F F UN I T 0 UT OUT P z H 5 V N O F R EQ C E CO ANCY PWR R E DUND V ON O F F S P F R EQ E T U P VOL T 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 2 2 0 0 6 0 ON O F F UN I T 0 UT OUT P z H...

Page 71: ...2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 2 2 0 0 6 0 ON O F F UN I T 0 UT OUT P z H 5 V N O F R EQ C E CO ANCY PWR R E DUND V ON O F F S P F R EQ E T U P VOL T 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 2 2 0 0 6 0 ON O F F UN I T 0 UT OUT P z H 5 V N O F R EQ C E CO ANCY PWR R E DUND V ON O F F 6 Redundancy Use or to select the desired...

Page 72: ...l parameters in this segment can only be changed under Bypass Mode L R P BAT Y TY P E 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 4 0 1 S S M D 0 8 1 0 0 1 1 0 1 0 0 1 1 0 E BAT T R I NG T A P E C E N E XT R L DAT E Y I N S T AL AH S E TU P M D DAT E Y S E C T A UR N I O T E S T D 3 Battery Strings Use or to select the desired number of battery strings then pres...

Page 73: ... S T D L R P BAT Y TY P E 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 4 0 1 S S M D 0 8 1 0 0 1 1 0 1 0 0 1 1 0 E BAT T R I NG T A P E C E N E XT R L DAT E Y I N S T AL AH S E TU P M D DAT E Y S E C T A UR N I O T E S T D L R P BAT Y TY P E 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 4 0 1 S S M D 0 8 1 0 0 1 1 0 1 0 0 1 1 0 E...

Page 74: ... O T A 3 UR R EN C G CHAR E R G S E TU P 1 Press to set the charging current E P R CHAR 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O T A 3 UR R EN C G CHAR E R G S E TU P 2 Press or to change the charging current then press to confirm Max possible charging current is 5A per module Press ESC to return to the UPS SETUP menu ...

Page 75: ...L P L E P ARA 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 1 GROU P L 1 D L P ARA I L E L S E TU P P ARA L L E L 3 PARALLEL ID Use or to set the UPS ID for parallel redundancy installation then press to confirm The ID is from 0 to 7 1 Use or to select the desired item then press to confirm 2 PARALLEL GROUP Use or to set the UPS group for parallel redundancy insta...

Page 76: ... Z E R 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O O F F DA I LY WE T E S T O I WE E KLY MONTH D I S AB L E R CONT B E T T R S T C L R BA UT A ARGE S O BO H C T F ORC E T AB L E T A B S E T MANUAL E N BUZ Z E R T E S T O P E Y L L KLY BAT E S UL T E S T L ED T BUZ Z E R 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O O F F DA I LY...

Page 77: ... AB L E T A B S E T MANUAL E N BUZ Z E R T E S T O P E Y L L KLY BAT E S UL T E S T L ED T BUZ Z E R 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O O F F DA I LY WE T E S T O I WE E KLY MONTH D I S AB L E OK R CONT B E T T R S T C L R BA UT A ARGE S O BO H C T F ORC E T AB L E T A B S E T MANUAL E N BUZ Z E R T E S T 5 Force Boost Charge Press to execute FORCE BOOS...

Page 78: ...ED LOAD UN UN I T 1 1 1 2 1 9 5 9 BY P A S S ON AUT O ME 0 8 1 0 0 2 1 2 1 D T I M Y M D M D Y D T 0 0 0 0 L LOCA MA W S A S D OR U S E R P Y S S P A D R WO ADM I N 5 0 A R NT S T L CD CO M O C D I S E R I AL DAT E R F O P M Y 9 5 9 DAT E 0 0 0 0 ENGL I S H GE LANGUA 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 2 1 9 5 9 BY P A S S ON AUT O ME 0 8 1 0 0 2 1 2 1 D T I M Y M D M D Y D T 0 0 0 0...

Page 79: ... S D OR U S E R P Y S S P A D R WO ADM I N 5 0 A R NT S T L CD CO M O C D I S E R I AL DAT E R F O P M Y 9 5 9 DAT E 0 0 0 0 ENGL I S H GE LANGUA 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 2 1 9 5 9 BY P A S S ON AUT O ME 0 8 1 0 0 2 1 2 1 D T I M Y M D M D Y D T 0 0 0 0 L LOCA MA W S A S D OR U S E R P Y S S P A D R WO ADM I N 5 0 A R NT S T L CD CO M O C D I S E R I AL DAT E R F O 5 LCD C...

Page 80: ... module T P 5 9 O P 1 0 CO ON BY P 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O 1 2 3 COUNT S D M 0 0 0 0 3 0 4 ME Y A ON B T I H S S A UNT S E RAT ON I 3 Statistics Use or to read the statistics data then press to confirm That will show the counts on battery counts on bypass and total operation time M P 2 0 0 1 3 o t e c P r PM 4 2 0 0 8 1 0 0 2 ROT E C T E D LO...

Page 81: ...0 u p I n t Ma i n s r m a l A b n o 4 Event Log Use or to read the event log then press to confirm C P D E 2 0 0 8 1 0 0 2 ROT E C T ED LOAD UN UN I T 1 1 1 1 5 9 5 9 BY P A S S ON AUT O N ADVA E D RA FW U P G O T HE R S T A C S S R C L T I S T I VE G E R C L NT LO 5 Advance Use or to select the ADVANCED item then press to confirm The ADVANCED item includes clear statistics clear event log firmwa...

Reviews: