1 General 

The external, manually operated bypass unit is an option for the 
PROTECT C.6000R UPS series in a rack version with 2U. It is 
used for disconnecting the UPS, for example for maintenance 
purposes, whilst the connected loads continue to be supplied 
without interruption. As well as solely bypass operation, an 
additional switch setting permits UPS test operation. Separately 
fused non-heating appliance connectors make it possible for the 
loads to be supplied directly from the MBS 6000. LEDs with 
various colours clearly signal which operating status has been 
selected. 

Scope of delivery: 

  External bypass unit MBS 6000 

  2 connection cables to the UPS 

 Operating instructions 

 

Prerequisite: 

  AEG UPS in the PROTECT C.6000R series 

 

Technical data: 

Nominal connection voltage / 

                              - frequency

 

230 VAC 50/60 Hz

 

Nominal current

 

32 A

 

Number of output sockets 

(load connection)

 

8

 

x IEC

 

320 C13 (10 A), 

fused in pairs 

by miniature fuse 

5 x 20 mm, T

 

10

 

additional non-fused  

output on terminal

 

Housing colour

 

blackline

 

Dimensions (HxWxD)  

         19-inch / rack operation

 

88 mm x 483 mm x 350 mm 

2

 

U x 19"

 

Summary of Contents for MBS 6000

Page 1: ...einheit für USV PROTECT C 6000R External Bypass Unit for UPS PROTECT C 6000R Typ Type MBS 6000 AEG Power Solutions GmbH Änderung Revision 01 Schenuit Schneider Datum Date 09 07 2009 Operating instructions 8000019069 BAL en ...

Page 2: ...ible for the loads to be supplied directly from the MBS 6000 LEDs with various colours clearly signal which operating status has been selected Scope of delivery External bypass unit MBS 6000 2 connection cables to the UPS Operating instructions Prerequisite AEG UPS in the PROTECT C 6000R series Technical data Nominal connection voltage frequency 230 VAC 50 60 Hz Nominal current 32 A Number of outp...

Page 3: ...ion bypass position i e load supply directly from the mains additional complete isolation of the UPS Attention UPS output may still be live due to its internal voltage source If there is a mains failure during TEST and BYPASS operation then the supply to the connected loads will be interrupted IMPORTANT UPS must be switched to BYPASS operation if external bypass switch will be operated refer to th...

Page 4: ... Output Rear view of MBS 6000 Connect the input of the external bypass to the mains connection cable provided with the UPS and plug the mains connector into a suitable shockproof socket In particular for types with high power ratings make sure that the fuse in your sub distribution system is sufficiently large Two connection cables are supplied with the external bypass Make the following connectio...

Page 5: ...5 5 Wiring diagrams UPS operation Service position Manual bypass NORMAL TEST BYPASS ...

Page 6: ...no Date of purchase Dealer stamp Signature Errors and changes excepted Emil Siepmann Straße 32 59581 Warstein Belecke Germany Tel 49 0 180 523 4787 Fax 49 0 180 523 4789 www aegpartnernet com Operating instructions 8000019069_01 BAL en ...

Reviews: