2 Description 

UPS Bypass Switch

USV Handumgehungsschalter

Achtung: Bedienungs-
anleitung beachten!

Attention: Refer to
operation instructions

UPS

UPS

UPS

NORMAL

SERVICE

BYPASS

Bypass

Test

Normal

Bypass

Test

Normal

 

The external bypass is used for changing over between 

¾

 "NORMAL" operation (default switch position), 

i.e. secure load supply with UPS back-up. 

¾

 "TEST" operation (service position), 

i.e. load supply directly from the mains, 
additional mains supply to the UPS for service purposes. 

¾

 "BYPASS" operation (bypass position), 

i.e. load supply directly from the mains, 
additional complete isolation of the UPS 
(Attention! UPS output may still be live due to its internal 
voltage source!) 

If there is a mains failure during "TEST" and "BYPASS" 
operation then the supply to the connected loads will be 
interrupted. 

IMPORTANT:

  UPS must be switched to “BYPASS” operation, 

if external bypass switch will be operated ! 
(refer to the UPS operating instructions) 

 

3. Installation 

(mechanical) 

During subsequent installation in the rack, take care that the unit is 
located close to the UPS so as firstly to establish the causal 
connection between the two and secondly to facilitate connection 
and subsequent replacement of the UPS. 

Summary of Contents for MBS 6000

Page 1: ...einheit für USV PROTECT C 6000R External Bypass Unit for UPS PROTECT C 6000R Typ Type MBS 6000 AEG Power Solutions GmbH Änderung Revision 01 Schenuit Schneider Datum Date 09 07 2009 Operating instructions 8000019069 BAL en ...

Page 2: ...ible for the loads to be supplied directly from the MBS 6000 LEDs with various colours clearly signal which operating status has been selected Scope of delivery External bypass unit MBS 6000 2 connection cables to the UPS Operating instructions Prerequisite AEG UPS in the PROTECT C 6000R series Technical data Nominal connection voltage frequency 230 VAC 50 60 Hz Nominal current 32 A Number of outp...

Page 3: ...ion bypass position i e load supply directly from the mains additional complete isolation of the UPS Attention UPS output may still be live due to its internal voltage source If there is a mains failure during TEST and BYPASS operation then the supply to the connected loads will be interrupted IMPORTANT UPS must be switched to BYPASS operation if external bypass switch will be operated refer to th...

Page 4: ... Output Rear view of MBS 6000 Connect the input of the external bypass to the mains connection cable provided with the UPS and plug the mains connector into a suitable shockproof socket In particular for types with high power ratings make sure that the fuse in your sub distribution system is sufficiently large Two connection cables are supplied with the external bypass Make the following connectio...

Page 5: ...5 5 Wiring diagrams UPS operation Service position Manual bypass NORMAL TEST BYPASS ...

Page 6: ...no Date of purchase Dealer stamp Signature Errors and changes excepted Emil Siepmann Straße 32 59581 Warstein Belecke Germany Tel 49 0 180 523 4787 Fax 49 0 180 523 4789 www aegpartnernet com Operating instructions 8000019069_01 BAL en ...

Reviews: