Time Current Curves (cold state), Protection Device
Auslösekennlinien (aus kaltem Zustand), Schutzgerät
Curve di intervento (a freddo)
0,1
1
10
100
1000
10000
1,00
10,00
100,00
x Breaker Rating In
ME10 Trip Unit -H & HE Trip Unit
- Time Current Curve
LT- Protection Device
Fuse type
- Band F-01
- Band F-05
- Band F-09
- Band F-13
- Band F-17
- Band F-21
2h
ST protection - OFF
I protection set to 15 x Ie
LT set at Breaker Rating
In
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
T
ripping time in Seconds (s)
0,1
1
10
100
1000
10000
1,00
10,00
100,00
x Breaker Rating In
ME10 Trip Unit -H & -HE Trip Unit
- Time Current Curve
LT- Protection Device
Fuse Type
- Band F-03
- Band F-07
- Band F-12
- Band F-15
- Band F-19
2h
ST protection - OFF
I protection set to 15 x Ie
LT set at Breaker Rating
In
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
T
ripping time in Seconds (s)
0,1
1
10
100
1000
10000
1,00
10,00
100,00
x Breaker Rating In
ME10 Trip Unit -H & -HE Trip Unit
- Time Current Curve
LT- Protection Device
Fuse Type
- Band F-02
- Band F-06
- Band F-10
- Band F-14
- Band F-18
- Band F-22
2h
ST protection - OFF
I protection set to 15 x Ie
LT set at Breaker Rating
In
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
T
ripping time in Seconds (s)
0,1
1
10
100
1000
10000
1,00
10,00
100,00
x Breaker Rating In
ME10 Tri Unit
-H & -HE Trip Unit
- Time Current Curve
LT- Protection Device
Fuse Type
- Band F-04
- Band F-08
- Band F-13
- Band F-16
- Band F-20
2h
ST protection - OFF
I protection set to 15 x Ie
LT set at Breaker Rating
In
Setting Range
Ie = 0.975, 0.9625, 0.95, 0.45 or 0.4 x In
Ir = 0.5 to 1 x Ie in steps of 0.25
T
ripping time in Seconds (s)