PROTECT C.R with 2 battery expansions
Fig.: PROTECT C. 2000 R and 2 units C. 2030 R BP
1.
Check the correct fit of the UPS and the battery
unit (compare the stated DC voltage on the label
of the UPS and the battery unit).
Never connect different battery voltage levels
with each other!
2.
Now connect the corresponding battery connectors
using the supplied battery connection cables as
shown in the figure above. When connecting, make
sure that you push the plug quickly and firmly in
the battery connectors.
To connect additional battery modules follow the procedure
explained above.
5.2.1
Electrical Start-Up
1. Verify that UPS voltage of your country
corresponds to your equipment voltage. The
default setting is set to 230 V. Output voltage on
the UPS system can be adjusted with the software
“CompuWatch” in steps of 220, 230 and 240 Vac.
Turn on the PROTECT C.R to the mains
To guarantee an accurate function of your UPS and all
additional devices, the mains have to be provides with the
corresponding protection. Connect the models PROTECT
C. 1000 R (S), C. 2000 R (S) and C. 3000 R (S) with the
29