Danger!
Danger!
Danger!
Danger!
The rated current of the utility power switch must be greater than the UPS input
current, otherwise the utility power switch may be burnt!
Recommended circuit breaker and contactor current specifications:
UPS power rating
Input mode
Breaker
Contactor
10000VA
1 phase main input
80A
≥80A
3 phase main input
32A
≥32A
1 phase bypass input
63A
≥63A
3 phase bypass input
32A
≥32A
15000VA
1 phase main input
125A
≥125A
3 phase main input
50A
≥50A
1 phase bypass input
100A
≥100A
3 phase bypass input
50A
≥50A
20000VA
1 phase main input
160A
≥160A
3 phase main input
63A
≥63A
1 phase bypass input
125A
≥125A
3 phase bypass input
63A
≥63A