12
2.3 Technical
Data
Type rating
PROTECT 1.100
10000 VA (cos
ϕ
= 0.7 ind.)
7000 W
PROTECT 1.150
15000 VA (cos
ϕ
= 0.7 ind.)
10500 W
PROTECT 1.200
20000 VA (cos
ϕ
= 0.7 ind.)
14000 W
UPS input
3ph~ / N / PE
Rated connection voltage
400 V/ 230 VAC
Voltage range without
304 VAC – 478 VAC ± 3 %
battery operation
(rectifier)
176 VAC – 261 VAC VAC ± 3 %
(bypass)
Frequency
50 Hz / 60 Hz
(autom. detection)
Frequency tolerance range
± 4 Hz
Current consumption at full load (max.)
PROTECT 1.100
13 A (3ph~) / 46 A (bypass)
PROTECT 1.150
19 A (3ph~) / 68 A (bypass)
PROTECT 1.200
25 A (3ph~) / 91 A (bypass)
System disturbance factor
λ
≥
0.95
UPS output
Nominal voltage output
220 / 230 / 240 VAC ± 1%
(configuration via
“CompuWatch” software )
Nominal frequency
50 Hz / 60 Hz ± 0.1%
(dependent on mains frequency)
Type of voltage
Sine, distortion
≤
2% THD (linear load)
≤
6% THD (non-linear load)
Crest factor
3:1