13
Overload behaviour
Up to 105% continuous;
with mains supply
> 105% – < 130% for 10 min.
130% for 1
s
Following this, automatic,
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min if overload
continues to be present. (Switch
back if overload decreases = load <
90%)
Overload behaviour with
Up to 105% continuous;
battery operation
> 105% for 10 s
Short-circuit behaviour
2.5 x I
N
for 100 ms
Battery
Standby times with external standard battery units
Standby times (full load / half load) [min.]
Coupled
battery cubicles
PROTECT
1.100
PROTECT
1.150
PROTECT
1.200
Recharging time
to 90% capacity
1 x PROTECT 1.100 BP
16 /
42 ---
---
5h
2 x PROTECT 1.100 BP
42 /
97 ---
---
7h
3 x PROTECT 1.100 BP
60 /
134 ---
---
10h
1 x PROTECT 1. BP 20
19 /
47
10 /
29
6 /
19
5h
2 x PROTECT 1. BP 20
47 /
103
29 /
68
19 /
47
9h
3 x PROTECT 1. BP 20
78 /
77
47 /
103
34 /
62
13h
4 x PROTECT 1. BP 20
103 /
243
68 /
153
47 /
103
18h
5 x PROTECT 1. BP 20
138 /
312
85 /
202
63 /
138
24h
Nominal DC voltage (intermediate circuit): 240 VDC
Trickle charge voltage: 274 VDC ± 1%
Battery charging current (max.): 4.2 ADC
Type Sealed,
maintenance-free
PROTECT 1.100 BP
2x20 blocks 12V 9Ah,
e.g. CSB HR 1234WF2
PROTECT 1.BP20
1x20 blocks 12V 20Ah,
e.g. Panasonic LC-X1220P