23
Please keep plastic packaging bags away from babies and
children in order to safeguard against suffocation accidents.
Handle the components with care. Please take into account the
weight. It may be necessary to engage the help of a second
person.
4.2
Transport to Installation Site
The PROTECT 1. is equipped with transport rolls for easy
transport to the intended installation site. It is recommended to
install the UPS where:
♦
The connection work can be conveniently carried out;
♦
There is enough space for proper operation and, if
necessary, for periodic and extraordinary maintenance
work; in this regard, the connection cables should be
long enough to move the UPS (to open the UPS if
necessary) without having to switch it off.
♦
The use of an external manual bypass is recommended
♦
The UPS is protected against external atmospheric
influences;
♦
The humidity and the ambient temperature are within the
limits;
♦
The fire protection standards are observed.
The battery service life strongly depends on the ambient
temperature. Ambient temperatures
15° and +
25°C
are optimum.
Attention!
Only transport the PROTECT 1.
in an upright
position
!
Never
tilt
or
cant
it; avoid displacing
the centre of gravity!
Make sure that no magnetic storage media are stored and/or
operated close to PROTECT 1.
4.3 Set-Up
Note the following points when setting up the UPS system and
its external battery units (special accessories):