15
Connection
Non-heating appliance
connectors
Current Crest Ratio
3:1
Overload behaviour
up to 105 % ± 5 % continuous;
in battery mode
> 105 % ± 5 % – < 150 % ± 5 %
for 25 s;
150 % ± 5 % for 200 ms
Overload behaviour
up to 105 % ± 5 % continuous;
with existing mains
> 105 % ± 5 % – < 150 % ± 5 %
for 30 s;
150 % ± 5 % for 300 ms
Then automatic inverter to
Bypass in < 4 ms (switches
back when overload damps =
Load < 90%)
Short circuit behaviour
3 x I
N
for 140 ms
Battery
Autonomy time (full load with internal battery)
PROTECT C. 1000
6 min
PROTECT C. 2000
10 min
PROTECT C. 3000
5 min
Autonomy time with external optional battery expansions
(only for PROTECT C. – models):
Coupled
Autonomy time (full load)
battery modules
C. 1000
C. 2000
C. 3000
1
38 min
55 min
30 min
2
76 min
106 min
60 min
Rated direct voltage (intermediate circuit)
PROTECT C. 1000 (S)
36 V
PROTECT C. 2000 (S)
96 V
PROTECT C. 3000 (S)
96 V