13
Overload behaviour
up to 105 % continuous;
in battery mode
> 105 % for 10 s
Short circuit behaviour
3 x I
N
for 300 ms
Battery
Autonomy time (full load with internal battery)
PROTECT C. 6000
8 min.
PROTECT C. 10000
5 min.
Autonomy times with external optional battery expansions
(only for PROTECT C. models):
Autonomy times (full load)
Coupled
battery modules
C.6000 C.
10000
1
25 min.
15 min.
2
45 min.
25 min.
3
60 min.
33 min.
Rated direct voltage (intermediate circuit)
PROTECT C. 6000 (S)
240 Vdc
PROTECT C.
10000 (S)
240 Vdc
Battery charging current
PROTECT C. 6000
2.0 A
PROTECT C. 6000 S
4.2 A
PROTECT C.
10000 2.0
A
PROTECT C.
10000 S
4.2 A
Recharge time
~ 7 h (UPS with internal
to 90% of rated capacity
battery only)
(PROTECT C. – models)
~ 11
h (with 1 battery
expansion)
~ 16 h (with 2 battery
expansions)
~ 24 h (with 3 battery
expansions)