24
5.1
UPS input connection
The system may be installed and wired only by qualified electricians in
accordance with applicable safety regulations! When installing the
electrical wiring, please note the nominal amperage of your incoming
feeder. Inspect the packaging carton and its contents for damage. Please
inform the transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use.
Note
: Please ensure that the incoming feeder is isolated and secured to
prevent it from being switched back on again.
If the UPS is connected via the power cord, please use a proper socket
with protection against electric current, the user can refer to below table.
If the UPS is connected via wires, it is recommended to select the 2.5mm
2
wire, and the “GND” terminal should be grounded first.
The UPS System has no input breaker on the standard cabinet. When
installing the UPS, the user needs to connect the external breakers and
protective components in the input terminals. It is recommended to select
the NFB (Non-Fuse Breaker) instead of the traditional combination kit
including breaker and fuse.
When selecting the NFB, the user can refer to below table.
Model
INPUT NFB & Power Cord & Socket
VOLTAGE
CURRENT
Protect D 1000(S)
LCD
300 VAC
10 A
Protect D 1500(S)
LCD
300 VAC
12 A
Protect D 2000(S)
LCD
300 VAC
16 A
Protect D 3000(S)
LCD
300 VAC
20 A
5.
ELECTRICAL CONNECTION