42
UPS On
USV Ein
UPS Off
Confirm: yes
no
USV Aus
Befehl bestätigen:
ja
nein
7.1 first start-uP
7.1.1 sWitchiNg ON thE uPs
attach the back-up fuse into your low-voltage main distribution (where the uPs
system was connected on the input side to the public network), or activate the
corresponding line circuit breaker. remember the supply for a separate bypass
feed-in.
the uPs will be immediately supplied with power from the public power network.
it will start up with an initialization phase, indicated by the aeg logo, which
appears on the screen for 5 seconds. after that, you will see the following
message:
now confirm the highlighted “uPs On” command by pressing “enter”. Hold the
key pressed for approx. 1 second. the uPs will synchronize and switch into normal
operating mode after just a few seconds. the display will switch to the uPs status
display.
if there are no keys pressed for 5 minutes, the display will automatically switch
back to the uPs status display. Press “
” to return.
7.1.2 sWitchiNg Off thE uPs
if the uPs is in operation, it is possible to access the command above by pressing
“
” when in the basic uPs status screen. Once you have confirmed the command
again, the uPs will switch off or switch to bypass (depending on the setting
selected).
7. oPeRAtIon MoDe AnD oPeRAtInG
Summary of Contents for Protect D. 10000 (BP)
Page 1: ...EN Protect D Protect D 6000 BP Protect D 10000 BP Operating Instructions ...
Page 2: ...2 ...
Page 20: ...20 3 3 CE certificate ...
Page 75: ...75 13 3 Notes ...