55
Description
Adjustable parameters
Presetting
Auto reboot
[enabled], [disabled]
"enabled " means the uPs outputs are
automatically reconnected after ensuing
switch-off, e.g. due to low battery voltage
after power is restored.
enabled
Auto bypass
[enabled], [disabled]
“enabled” means uPs will have bypass
output when utility power on.
“Disabled” means uPs will not have bypass
output when power is on but could get
bypass output when uPs is in fault or overload.
enabled
start-up without
battery
[enabled], [disabled]
"active" means the uPs can be started
without installed battery system.
disabled
Clear event log
the number after “total events” shows how
many events are currently stored in the log.
Press the “enter” button for one second to
reset the event count to zero and clear the log.
—
lCD Contrast
[-5], [-4], …[-1], [0], [+1], …[+4], [+5]
the LcD contrast is adjustable and the valid
range is from -5 to +5.
0
Restore factory
settings
[no], [yes]
setting only available in uPs stand-by mode.
• restoring the factory settings:
• returns all user-configurable settings to
default factory settings
• resets all pending on / off commands
• clears the alarm and event log
• after acknowledgement the uPs
conducts a new initialization process
no
the “restore Factory settings” process is completed after the uPs is switched
off completely. Wait until the fans stopped to prevent the uPs internal eePrOM
overwriting.
Summary of Contents for Protect D. 10000 (BP)
Page 1: ...EN Protect D Protect D 6000 BP Protect D 10000 BP Operating Instructions ...
Page 2: ...2 ...
Page 20: ...20 3 3 CE certificate ...
Page 75: ...75 13 3 Notes ...