52
OMD94016 REV. C
Alarm
A36 DC FASTSHUTDOWN
Description
Inverter shutdown due to the operation of the protection
sensor as a result of sudden DC voltage variations.
Possible
causes
•
Battery fault.
Solutions
1) Check the battery.
2) Reset the system.
3) If the alarm persists, contact our Technical Support
Service.
Alarm
A38 INV LOAD
Description
The load is fed by the inverter. This alarm is active for UPS
systems in “ECO” mode, where the preferential supply is
from the bypass line.
Possible
causes
•
Temporary changeover due to bypass line failure.
Solutions
1) Verify the status of the bypass line and check whether
other alarms are present.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A39 INV ERROR LOOP
Description
The control is not able to regulate the inverter voltage
precisely.
Possible
causes
•
Regulation system failure.
Solutions
1) Reset the system.
2) If the alarm persists, contact our Technical Support
Service.
Alarm
A40 SSI FAULT
Description
The system has detected a failure in the static inverter
switch.
Possible
causes
•
Possible problems on the loads.
•
Static switch fault.
Solutions
1) Check the absorption of the loads and the presence of
DC components, if any, on AC current.
2) If the alarm persists, contact our Technical Support
Service.