7
To connect the met[LOG] to LAN, please use a commercially available Ethernet cable.
For outdoor use, please make sure you apply materials that are approved accordingly, e.g. the
power[cube] and UV-resistant cables.
Upon delivery, the met[LOG] is configured to an assigned IP-address from the DHCP server automati-
cally.
An alternative IP-address can be chosen by using a special configuration.
Connecting to power supply
The dot (cycle) on the front side points in the direction of terminal 1.
The met[LOG] can be supplied with 11…32 VDC.
For power supply connection, use terminal 16 „+Power 11…32VCD“ and terminal 15 „System
Ground“.
Attention!
All analogue and digital inputs and all digital outputs refer to the „System Ground“.
Note:
The supply voltage is switched to the digital outputs depending on the configuration
and the alarm settings.