9
A
...
and ~
40 mA
400 mA
10 A
Voltage
200 mV
1 V
400 mV
drop
(1)
Digital
1 µA
10 µA
1 mA
resolution
Bargraph
0.1 mA
1 mA
100 m A
resolution
Accuracy
± 0.5% rdg ± 5 counts
± 1.5% rdg
in DC
± 10 counts
Accuracy
(2)
± 0.9% rdg ± 10 counts
± 1.5% rdg
in AC
± 5 counts
Protection
(3)
Fuse 0.5 A HBC
Fuse 12 A HBC
(1) Voltage drop at terminals fo r 40 mA, 400 mA, 10 A
Peak factor FC
≤
3 (full scale) and FC
≤
6 (mid-scale)
(2) Use for 40 Hz to 1000 Hz frequencies
(3) Admissible overloads : 12 A for 30 seconds for 10 A measurements
600 mA for 30 seconds for 400 mA measurements
9 - GENERAL SPECIFICATIONS
9-1 Dimensions and weight
!
2.5 x 7 x 1.7 " (64 x 177 x 42 mm)
!
12.3 ounces (350 g)
9-2 Power supply
!
One battery 9 V
!
Autonomy : 200 hrs with type 6 F22 battery
400 hrs with alkaline type 6 LF 22 battery
!
Indication of battery wear :
+
-
!
Automatic cut-out after 30 minutes
Note : Restart from the OFF position
9.3 Buzzer
!
Continuous audible beep for the continuity test
!
Intermittent audible beep each time the switch and buttons are
activated and to indicate overruns.
9-4 Climatic conditions
!
Temperature : use : 0°C to +50°C / storage : -20°C to +60°C
!
Relative humidity : use :
≤
70% RH
storage :
≤
80% RH
!
Altitude : use < 2000 m
9-5 Conformity with international standards
9-5-1
Electrical safety (as per IEC 1010-1)
!
Double insulation :
!
Installation category : III
!
Degree of pollution : 2
!
Assigned voltage : 600 V RMS
Note : This overload category III multimeter conforms to the strict
reliability and availability requirements corresponding to fixed industrial
and domestic installations (IEC 664-1).