background image

WJ-5000/5200 SERIES

WJ-5000/5200 SERIES

10

09

5.Advanced parameters adjustment case:

0

.

5

1

2

3

4

5

6

7

8

9

10

F0

F1

F2

F3

F4

F5

F6

F7

F8

F9

25

-2

-2

0

.

1

0

10

15

45

8

30

20

-3

1

10

10

45

8

31

25

28

2

.

0

0

5

10

45

8

30

5

25

1

.

0

0

4

14

45

8

30

5

25

0

.

8

1

10

15

45

8

30

20

Temperature

 

setting

Temperature

Difference values

Cooling

 

hysteresis

Alarm for over high

water temperature

Alarm for over low

water temperature

Alarm for over high

room temperature

The allowed highest

water temperature

The allowed lowest
water temperature

Way of control

Password

Order

Code

Item

Value in

case 1

Value in

case 2

Value in

case 3

Temperature 

Controller 

Factory Setting     

Temperature 

Controller 

Factory Setting     

T504

T503

(

1

)

Case 1: cooling water temperature is controlled by intelligent   mode. Requiring water temperature to be between 25

to

 

31

.  Ambient  temperature

 

keeping

 

constant,  when  the

 

set  water  temperature

 

is  3

lower  than  the  ambient,  the

 

fluctuation will not exceed

 

±0.5

.There will be an alert  when  water

 

temperature is

 

10

 lower or

 

higher

 

than target. 

(e.g.when ambient

 

temperature is 30.0

, cooling water temperature is between 27.5

to 26.5

,if ambient temperature is 

up to  30.5

, water temperature will be between  28.0

 to 27.0

.)

(

2

)

Case 2: cooling  water temperature is controlled  by constant mode.  Requiring

 

water temperature is constant in 28

℃, 

and the fluctuate does not exceed ±2

.The alarm of over high water temperature will be on when water temperature is

 

5

 higher than normal, and the alarm of over low water temperature will be on

 

when water temperature is 10

 lower 

than normal.

(

2

)

Case 3: cooling  water temperature is controlled  by constant mode.  Requiring water temperature is constant in 25

℃, 

and the fluctuate does not exceed±1

.The over  high water temperature  will be on then water temperature  is higher

 

than 30

,  and the alarm of over low water  temperature will be on when water

 

temperature is  lower than 10

. (No  

matter what  is the ambient  temperature,the cooling water temperature is constant in 24.0

 to 26.0

)

<5>

 

Flow alarm and output ports

In order to guarantee the equipment will not be damaged while cooling water circulation is out of 
control, WJ-5000/5200series chillers possesses an unique low flow alarm protection.

1.Flow alarm output ports and the wiring diagram

2.Flow alarm causes of circulating cooling water and working state

Flow-sw

BZ

Red light

Green light

Alarm outpout ports

Output poorts diagram

OFF

ON

OFF

OFF

OFF

ON

ON

ON

Breakover

Disconnection

Disconnection

Disconnection

Disconnection

Breakover

Disconnection

Breakover

Breakover

Breakover

Output ports

H1 H2

Output ports

H1 H3

Buzzer

Flow 
indicator

alarm 

Normal 
indicator

flow

DISPLAY

CONDITION

Note: The flow alarm  is connected to the normally  open relay and normally  closed

 

relay contacts, requiring 

operating current less than 5A, working voltage less

 

than 300V. 

Circulating pump works properly

Blocked cooling water

circulation loop

Alarm of water shortage

Faulted circulating pump

Power interruption

OFFICIAL DISTRIBUTOR  UAB ELTECHNIKA 

WWW.AEONLASERS.LT | WWW.AEONLASERS.LV | WWW.AEONLASERS.EE

Summary of Contents for WJ-5000 Series

Page 1: ...SER MANUAL USER MANUAL 1 Cautions 2 Parts introduction 3 Installation 4 Operation and 5 Flow alarm and 6 Specifications 7 Simple troubleshooting CONTENTS parameters adjustment output ports 03 04 05 06...

Page 2: ...o please make sure the tank has water inside before machine starting otherwise it s easily to have the pump damaged When the water level is below the green NORMAL range of the water level gauge the co...

Page 3: ...te water again Please observe and record the current water level and inspect it again after the chiller running for a period of time if the water level drops obviously please re inspect the water pipe...

Page 4: ...ess key to change settings After modifying the value press the ENTER button RST to save and exit then new parameters take effect or press SET key SET to exit without saving parameters If there is no m...

Page 5: ...is 5 higher than normal and the alarm of over low water temperature will be on when water temperature is 10 lower than normal 2 Case 3 cooling water temperature is controlled by constant mode Requiri...

Page 6: ...on functions are optional 2 WJ 5200 Series compressional type chiller With heating and higher temperature precision functions are optional Model Voltage Frequency Current Compressor power Refrigeratio...

Page 7: ...olysis Poorventilationforairoutletandinlet Voltageis extremelylowor astable Improperparametersettingson thermostat Excessiveheatload Theworkingambienttemperatureis too highforthechiller Watertemperatu...

Reviews: