WJ-5000/5200 SERIES
WJ-5000/5200 SERIES
10
09
5.Advanced parameters adjustment case:
0
.
5
1
2
3
4
5
6
7
8
9
10
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
25
-2
-2
0
.
1
0
10
15
45
8
30
20
-3
1
10
10
45
8
31
25
28
2
.
0
0
5
10
45
8
30
5
25
1
.
0
0
4
14
45
8
30
5
25
0
.
8
1
10
15
45
8
30
20
Temperature
setting
Temperature
Difference values
Cooling
hysteresis
Alarm for over high
water temperature
Alarm for over low
water temperature
Alarm for over high
room temperature
The allowed highest
water temperature
The allowed lowest
water temperature
Way of control
Password
Order
Code
Item
Value in
case 1
Value in
case 2
Value in
case 3
Temperature
Controller
Factory Setting
Temperature
Controller
Factory Setting
T504
T503
(
1
)
Case 1: cooling water temperature is controlled by intelligent mode. Requiring water temperature to be between 25
℃
to
31
℃
. Ambient temperature
keeping
constant, when the
set water temperature
is 3
℃
lower than the ambient, the
fluctuation will not exceed
±0.5
℃
.There will be an alert when water
temperature is
10
℃
lower or
higher
than target.
(e.g.when ambient
temperature is 30.0
℃
, cooling water temperature is between 27.5
℃
to 26.5
℃
,if ambient temperature is
up to 30.5
℃
, water temperature will be between 28.0
℃
to 27.0
℃
.)
(
2
)
Case 2: cooling water temperature is controlled by constant mode. Requiring
water temperature is constant in 28
℃,
and the fluctuate does not exceed ±2
℃
.The alarm of over high water temperature will be on when water temperature is
5
℃
higher than normal, and the alarm of over low water temperature will be on
when water temperature is 10
℃
lower
than normal.
(
2
)
Case 3: cooling water temperature is controlled by constant mode. Requiring water temperature is constant in 25
℃,
and the fluctuate does not exceed±1
℃
.The over high water temperature will be on then water temperature is higher
than 30
℃
, and the alarm of over low water temperature will be on when water
temperature is lower than 10
℃
. (No
matter what is the ambient temperature,the cooling water temperature is constant in 24.0
℃
to 26.0
℃
)
<5>
Flow alarm and output ports
In order to guarantee the equipment will not be damaged while cooling water circulation is out of
control, WJ-5000/5200series chillers possesses an unique low flow alarm protection.
1.Flow alarm output ports and the wiring diagram
2.Flow alarm causes of circulating cooling water and working state
Flow-sw
BZ
Red light
Green light
Alarm outpout ports
Output poorts diagram
OFF
ON
OFF
OFF
OFF
ON
ON
ON
Breakover
Disconnection
Disconnection
Disconnection
Disconnection
Breakover
Disconnection
Breakover
Breakover
Breakover
Output ports
H1 H2
Output ports
H1 H3
Buzzer
Flow
indicator
alarm
Normal
indicator
flow
DISPLAY
CONDITION
Note: The flow alarm is connected to the normally open relay and normally closed
relay contacts, requiring
operating current less than 5A, working voltage less
than 300V.
Circulating pump works properly
Blocked cooling water
circulation loop
Alarm of water shortage
Faulted circulating pump
Power interruption