WJ-5000/5200 SERIES

WJ-5000/5200 SERIES

14

13

<7>

 

Simple troubleshooting

FAILURE

FAILURE CAUSE

APPROACH

Check and ensure the power

 

interface and the 

power plug is

 

plugged in place and in good contact.

Power cord is not plugged in place

Fuse burnt-out

Pull out the fuse box from the power supply 

interface of the chiller, check the fuse, replace with 

spare fuse if necessary and check whether the 

power supply voltage is stable; Check and ensure 

the power interface and the power plug is plugged in 

Check the water level gauge display, add water 

until the level shown in the green area; And check 

whether water circulation pipe leaks.

Check water circulation pipe

Flow Alarm (panel red light is 
on)use a water pipe directly 
connect to the water outlet and 
inlet but still without water flowing

Machine turned on but 
unelectrified

Ultra-high 
temperature alarm

Alarm for ultra-high room temperature

Serious problem of condensate water

Water drains slowly from outfall 
during water changing

Switch the power frequently

Blocked dust gauze, bad thermolysis

Poor ventilation for air outlet and inlet

Voltage is extremely low or astable

Improper parameter settings on thermostat

Excessive heat load

The working ambient temperature is too

 high for the chiller

Water temperature is much lower than
ambient temperature, with high humidity

Injection port is not open

Open the injection port

Increase water temperature or

 

to preserve heat 

for pipeline

To improve the ventilation to guarantee that the 

machine is running under 40

℃.

Reduce the heat load or use

 

other model with

 larger cooling

 

capacity

To ensure there is sufficient time

 

for refrigeration

(more than 5 minuets)

To reset controlling parameters

or restore factory settings

To improve the power supply

circuit or use a voltage regulator

To ensure a smooth ventilation for air outlet and inlet

To ensure a smooth ventilation for  air outlet and inlet

Water level in the storage 

water tank is too low

Water circulation pipes are blocked 

or apipe bending deformation.

<4>

 

P

acking

 

list

1.1 unit of industrial chiller.
2.1 copy of user manual.
3.1 pc of power cord.
4.1 pc of alarm signal output plug.
5.1 pc of spare fuse.

(held in the spare fuseholder of power socket.)

OFFICIAL DISTRIBUTOR  UAB ELTECHNIKA 

WWW.AEONLASERS.LT | WWW.AEONLASERS.LV | WWW.AEONLASERS.EE

Summary of Contents for WJ-5000 Series

Page 1: ...SER MANUAL USER MANUAL 1 Cautions 2 Parts introduction 3 Installation 4 Operation and 5 Flow alarm and 6 Specifications 7 Simple troubleshooting CONTENTS parameters adjustment output ports 03 04 05 06...

Page 2: ...o please make sure the tank has water inside before machine starting otherwise it s easily to have the pump damaged When the water level is below the green NORMAL range of the water level gauge the co...

Page 3: ...te water again Please observe and record the current water level and inspect it again after the chiller running for a period of time if the water level drops obviously please re inspect the water pipe...

Page 4: ...ess key to change settings After modifying the value press the ENTER button RST to save and exit then new parameters take effect or press SET key SET to exit without saving parameters If there is no m...

Page 5: ...is 5 higher than normal and the alarm of over low water temperature will be on when water temperature is 10 lower than normal 2 Case 3 cooling water temperature is controlled by constant mode Requiri...

Page 6: ...on functions are optional 2 WJ 5200 Series compressional type chiller With heating and higher temperature precision functions are optional Model Voltage Frequency Current Compressor power Refrigeratio...

Page 7: ...olysis Poorventilationforairoutletandinlet Voltageis extremelylowor astable Improperparametersettingson thermostat Excessiveheatload Theworkingambienttemperatureis too highforthechiller Watertemperatu...

Reviews: