10
In order to take out the components for reasons such as cleaning, maintenance and replacement, While locating the
unit, gaps of appropriate sizes should be left around the unit. This space should be on the service side of the unit and
at least 1.2 times the width of the unit.
If the units are to be operated in an outdoor application, they should be specified
before the project selection and should be produced in accordance with the outdoor application. (weather protection
sheet, high protection class component selection etc.). Otherwise, the unit should not be operated outside.
3.2 Module Combination
Labels are placed on the modules to facilitate the assembling of the modules.
Sealing gaskets are applied between the modules of air handling units. Before the modules are combined, the gaskets
should be checked and if there is any damage, replaced with new ones.
ATTENTION