Care should be taken when connecting ducts to the dampers in the openings
of the device to the outside. If the screws get stuck in the gear of the damper mechanism, the damper will not work.
Therefore, the following points should be considered in the duct mounting to be made on dampers.
•
The duct connection of the dampers should be made via the bolt holes in the corners.
•
Gaskets must be applied between dampers and duct connections.
•
In places other than these holes, the screws should be tightened in a way that they are a maximum of 10mm inside
from the edge.
•
In order to prevent air leakage G clips should be used to the areas between the screws.
Max. 10mm
Gaskets
must
be
used
between the duct and damper and flange connection surfaces. In
order to tighten the gaskets properly, G-Clips should be placed on
the connections at a maximum of 25 cm intervals.
Duct connections on the unit are indicated with the labels below.
While making the connection, make sure that the correct duct is
connected to the right place.