20
Documents
containing
the
electrical and automation details of the air handling unit are attached to
the automation panel or the module with the accessories. All electrical
connections must be made according to this document.
3.12.1.1
Control Panel and BMS Connection
Air handling units that are requested with automation equipment can be integrated with the building automation system
via Modbus TCP-IP / Bacnet protocols and can be monitored with these protocols. Ethernet (RJ45) port on the con-
troller located in the unit automation panel should be used for BMS connection.
Terminals are reserved on the automation panel for external display connections (E3-DSP/ED-T7). Screen connec-
tions must be made with 4x0.50 shielded cable. The maximum wiring distance for touch panel (ED-T7) and standard
display (E3-DSP) is 100 m.
3.12.2
Air Handling Unit without Automation Equipment
The electrical connection of the unit should only be made by qualified
electricians.
Before all electrical assembly operations, the main supply panel must be de-
energized and it must be ensured that it cannot be energized accidentally.
Your air handling unit can be manufactured specifically for the project with or without the automation panel. The
wiring diagrams placed inside the unit must be examined against the different variations of the unit.
BMS
BacNet IP
ModBus TCP
CAUTION
External Display
DANGER
DANGER