18
6 COMMISSIONING AND OPERATION
6.2.1 Setting of the continuous running (low) speed
To set the continuous running (low) speed use the dip switches 1-2-3.
DIP1
DIP2
DIP3
Low speed
m
3
/h
l/s
0
0
0
104
29 (default)
0
0
1
61
17
0
1
0
76
21
0
1
1
90
25
1
0
0
119
33
1
0
1
133
37
1
1
0
148
41
1
1
1
162
45
DIP4
Maximum speed
m
3
/h
l/s
0
216
60 (default)
1
180
50
6.2.2 Setting of the maximum speed
To set the maximum speed use the dip switch 4.
6.1
1
1
0
DIP SWITCHES
2 3
4
1
1
0
DIP SWITCHES
2 3
4
The unit runs at the set continuous running speed (low). The maximum speed can be activated by means a remote dedicated
switch (wiring diagram Fig. 5.i).
The speeds can be set during the commissioning according to the ventilation rate needed, by means of the trimmer V1 and V2
(Fig.6.a).
Factory setting (default):
V1 (min speed) 104m
3
/h (29l/s).
V2 (max speed) 216m
3
/h (60l/s).
6.2
1 2 3
4
V1
V2
N
L
S1 S2 S3 GND
GND POT +10
Fig. 6.a
A (min)
B
C
D
E
F
G (max)
TRIMMER
Trimmer position
m
3
/h
l/s
W
A (min)
61
17
3,7
B
76
21
4,3
C
104
29
7,5
D
144
40
12,0
E
180
50
17,3
F
198
55
21,0
G (max)
216
60
24,2
AIRQURE P1-N
AIRQURE P1-H