15
WARNING: regardless of the control system in place (potentiometer or ModBus), it’s strongly recommended to
wire the ModBus communication line and make it accessible from ground level, in order to ease troubleshooting
via ModBus anytime after the installation.
9. CLEANING
The unit (IP65) can be washed with water jets. In this case it is recommended to drill a hole under the plastic cover for water drainage.
10. TROUBLESHOOTING (ModBus)
10.1 Connection parameters
Protocol
MODBUS/RTU over RS485
Baud Rate (bps)
9600
Data bits
8
Parity bits
none
Stop bits
2
HVLS Slave Address
1
10.2 ModBus Registers - Input Register
These registers are READ-ONLY, and can be read using the function
04 READ INPUT REGISTERS.
Register
Address
Description
Dimension
(Word)
Data
Type
U.M. (data on
the register)
Example
Register value
→
Real value
3
Measured speed
1
ushort
0.1rpm
490
→
49rpm
10
Alarm 1
1
ushort
-
See table (§ 10.3)
17
Alarm 2
1
ushort
-
See table (§ 10.3)
33
Minutes Time Counter
1
ushort
Minutes
23
→
23 Minutes
Start to Count when Motoinverter is On.
Store lifetime data
34
Hours Time Counter
1
ushort
Hours
1234
→
1234 Hours
Start to Count when Motoinverter is On.
Store lifetime data
POT.
CTRL-A (ACCESSORY ON REQUEST)
YELLOW-GREEN
BROWN
BLACK
GREY
L1
L2
L3
400 Vac
3 ph.
50/60 Hz
BROWN
YELLOW
GREEN
BOBINA
230V
BIPOLAR
SWITCH
230V
+
U
-
CTRL - A
6-core control cable
EXTERNAL CONTACTOR
(NOT SUPPLIED)
4-core power cable
WHITE
GREY
PINK
X
MODBUS B
MODBUS A