Two speed operation
Fig. 5.q
CTRL-M
(accessory on request)
Fig. 5.r
CTRL-S
(accessory on request)
I
I I
X : Dip 1 switch is for factory setting only and it does not have to be changed.
5.p
1 2 3 4
operation
X
0
0
0
Single speed
X
1
0
0
Two speed
X
0
1
0
Variable speed with CTRL-M remote manual controller
X
0
1
1
Variable speed throught external domotic (BMS) system or ballast potentiometer
X
1
1
0
Three speed with CTRL-S
Dip switch
1
2 3 4
1
0
6 commIssIoNINg
6.1 Setting Fan speed
The speed of the unit can be adjusted during installation according to required ventilation rate.
Figure 6.a
below shows performance curves (for supply air and extract air) at different settings of the 0-10V signal to the motors. Airflow and consumption
refer to one single motor.
Table 6.b
indicates the efficiency of the heat exchanger and of the condensation produced in different climatic conditions, to help the installer or the designer
of the ventilation system to decide if to connect one or both condensation drainages.
High production of condensation is the direct consequence of a high efficiency level as well as of the humidity rate.
Table 6.c
indicates the sound level at the different speed.
Static Pressure - Pa
Air-flow - m3/h
A
B
C
D
E
F
G
TrimmEr V1- V2
0
50
100
150
200
250
300
350
400
450
500
550
600
0
50
100
150
200
250
300
350
I
III
IV V
VI
II
A
B
C
D
E
F
G
Fig. 6.a
Intake curve according to Reg. 1253/2014
curve
speed
%
W
max
m
3
/h
max
A (min)
20
8
43
B
35
24
103
C
50
70
185
D
60
98
215
E
67
155
263
F
85
275
330
G (max)
100
325
346