18
ALARM 1
VALUE
ALARM 2
VALUE
ALARM DESCRIPTION
POSSIBLE CAUSE
TROUBLESHOOTING
0
0
No error
-
1
0
Memory error – motor parameters lost
Contact manufacturer/technical support
2
0
Short circuit – electronics power
module damaged
Board damaged – replace board
3
0
Motor synchronization lost – wrong motor parameters
or electronics damaged
Check motor windings.
If motor windings OK (all 3 windings have same resistance),
replace board.
If motor windings damaged (open/short circuit), replace motor.
4
32
Over voltage: supply voltage above 565Vac (DC bus
voltage over 800V) during motor running
Check power supply voltage
check power supply wiring
4
33
Under voltage: supply voltage below 212Vac (DC bus
voltage below 300V) during motor running
Check power supply voltage
check power supply wiring
4
113
Electronics temperature over 85°C
(check input register 15)
Check if operating temperature is above rated maximum operating
temperature.
Check mechanical load for anomalies (e.g. difficult turning)
4
114
Motor windings temperature over 125°C
(check input register 16)
Check if operating temperature is above rated maximum operating
temperature.
Check mechanical load for anomalies (e.g. difficult turning)
11.3 Alarm codes/LED status/Troubleshooting
For additional information on HVLS Modbus control, contact the manufacturer/technical support.