AERCO Control System (ACS)
APPENDIX B:
Status and Fault Messages
11/22/2017
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
Page 101 of 139
OMM-0081_0F
Phone: 800-526-0288
GF-131
TABLE B-6: BMM (Boiler Management Module) Fault Codes
Code
Description
Effect
Correction
Reset
27
Air flow failure
during ignition.
Restart pre-purge
timer. The failure
remains until we
have a successful
burner operation.
Check fan and wiring.
Check air proving switch
and wiring.
AUTOMATIC
30
Settings Corrupted
Ignition is
inhibited. Pump
runs for 5 min at
max speed.
Re-program the settings.
Contact Factory
MANUAL - cycle the
power or send reset
message.
32
Line voltage too
low. (<96 VAC)
Wait for proper
line voltage. (>102
VAC)
Check input voltage else
try another BMM.
AUTOMATIC
40
Low Water Flow.
Low water flow
switch activated.
Burners turned
OFF.
Check water flow or
check switch.
AUTOMATIC