B.6 BMM (BURNER MANAGEMENT MODULE) FAULT CODES
TABLE B-6: BMM (Boiler Management Module) Fault Codes
Code
Description
Effect
Correction
Reset
1
High Limit (STB)
Thermostat
activated
All burners turned
OFF and Pump
ON at maximum
speed.
Check FlowSensor
thermal connection to
boiler.
MANUAL - push reset
switch when
temperature goes
below limit.
2
Low Gas Pressure
All burners turned
OFF .
Check gas pressure or
gas pressure switch.
AUTOMATIC - when
gas pressure switch
closes.
4
No flame detected
at burner start
Burner control
lockout.
Check flame rod or
combustion.
MANUAL - push reset
switch or cycle power.
5
Flame loss during
run.
Ignition retry.
Check combustion and
wiring.
MANUAL - push reset
switch or cycle power.
6
High outlet
temperature.
FlowSensor
temperature >
203°F.
All burners turned
OFF and Pump
ON at maximum
speed.
Check Flow Sensor or
system pump
AUTOMATIC - when
FlowSensor < 176°F.
10
Internal Failure
Ignition is
inhibited.
Contact Factory for new
BCM.
MANUAL - cycle the
power.
11
Flame signal
detected before
ignition.
Ignition is
inhibited.
Disconnect flame rod wire
from BMM. If problem
goes away change flame
rod and/or wire. If
problem does not go
away change BMM.
MANUAL - push reset
switch or cycle power.
12
FlowSensor fault.
All burners turned
OFF.
Check flow sensor or
wiring.
AUTOMATIC
14
Return Sensor
fault
All burners turned
OFF.
Check return sensor or
wiring.
AUTOMATIC
15
Maximum Δ-
temperature
protection. Flow
temperature -
Return
Temperature >
Water Δ-Temp
Prot 50°F
All burners turned
OFF and Pump
ON at maximum
speed.
Check the system
installation.
AUTOMATIC -
when Δ-
temperature <
Water Δ-
Temp Protection.