AERCO Control System (ACS)
CHAPTER 3
: Operation
11/22/2017
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, New York 10913
Page 53 of 139
OMM-0081_0F
Phone: 800-526-0288
GF-131
Setting up an Offset Schedule
1.
Scroll through the
FIELD ADJUST MENU
and select
OFFSET ENABLE
. Set this option to
ON.
2.
Next, scroll to
SUN OFFS TEMP
and set the Offset Temperature to
-15°F
.
3.
Press the ▲ arrow key.
SUN ON HOUR
will be displayed. Set the
HOUR
to
00.
4.
Press the ▲ arrow key again.
SUN ON MINUTE
will be displayed. Set the
MINUTE
to
01.
5.
Press the ▲ arrow key again.
SUN OFF HOUR
will be displayed. Set the
HOUR
to
08.
6.
Press the ▲ arrow key again.
SUN OFF MINUTE
will be displayed. Set the
MINUTE
to
00.
7.
Repeat steps 2 through 6 to set offset schedules for the remaining days of the week.
Different offset temperatures and ON/OFF times can be set for each day if desired.
3.8.11 Setting up a Manual Offset Schedule
If a switch is connected across terminals 13 and 14 on the ACS, the offset temperature can be
controlled manually. To set up a manual offset schedule, proceed as shown below.
Setting up a MANUAL Offset Schedule
1.
Scroll through the FIELD ADJUST MENU and select OFFSET ENABLE. Set this option to
ON
2.
Next, scroll to SUN OFFS TEMP and set the desired Offset Temperature. A different Offset
Temperature can be set for each day if desired.
3.
Scroll through the remaining days of the week and set desired offset temperature for each
day.
Once programmed as described above, closing the SET BACK switch will enable the
programmed
OFFS TEMP
for that day. Opening the SET BACK switch will disable the
OFFSET
and the Header Setpoint will return the selected
INTERNAL SETPT
temperature.
CONFIGURATION MENU
3.8
The Configuration Menu contains options which set the Boiler operating modes start/stop levels
and maximum allowable power input. In addition, it contains a Fail Safe Mode feature which is
used to select the default mode when the controlling input source is lost.
3.9.1 BLR CNTL SELECT
You can select the type of boiler control being connected to the ACS (C-More or BCM) in order
for the ACS to read its Outlet Temp and Error Code in the Operating Menu. Otherwise, select
NONE to disable these displays in the Operating Menu.
3.9.2 BOILER OP MODE
The
BOILER OP MODE
menu option sets the control operation method for the ACS to either
SEQUENTIAL
or
PARALLEL MODE
.