AM Series Boilers and Water Heaters
CHAPTER 3: INSTALLATION - SITE
Page
32
of
154
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0100_0D
03/28/16
Ph.: 800-526-0288
GF-146
Installing the 119-Gallon Tank - Continued
7. Install the thermowell (P/N 49263) into the lower port on tank (see Figure 3-16) with pipe
dope, then put heat conducting compound (P/N 122848) inside the thermowell.
8. Put the temperature sensor probe through the cord grip (P/N 62005) and then insert the
sensor fully into the thermowell (see Figure 3-16). Screw the cord grip into the thermowell
and then tighten cord grip to secure the temperature sensor probe in the thermowell.
9. Install pressure relief valve (P/N 92129) into upper port of tank using appropriate pipe dope
(such as Loctite 567). Valve outlet should point downwards (Figure 3-16).
Figure 3-16: AMR 119-Gallon Tank Installation and Components
10. Install a reducing coupler
(P/N 93499)
into both the tank INLET and OUTLET to reduce
both connections from 2-1/2” to 2”.
11. Install a 3” nipple (P/N 90046-3) into the reducing couplers installed in the tank’s INLET and
OUTLET in Step 10.
12. Connect 24” flex hose (P/N 97084-24) between nipple in the tank INLET and AMR OUTLET.
13. Connect 18” or 24” (see NOTE) flex hose between nipple in the tank OUTLET and AMR
recirculation loop INLET (Figure 3-16).
14. Double-check that all water connections on the rear of the unit are tight and have not
loosened during shipping.
NOTE:
Use 18” hose (P/N 97084-18) for 399/500 units & 24” hose (P/N 97084-24) for
750/1000 units.
STEP 6:
TIGHTEN
TANK
CLAMPS
STEP 7:
INSTALL
THERMO-
WELL
STEP 9:
INSTALL
P&T VALVE
STEP 12:
INSTALL 24”
FLEX HOSE
119 GALLON
BUFFER
TANK
AMR
RECIRC.
LOOP
INLET
TANK
OUTLET
AMR HOT
WATER
OUTLET
TANK
INLET
STEP 13:
INSTALL
18” (399/500)
OR
24” (750/1000)
FLEX HOSE
STEP 10:
INSTALL
REDUCER
COUPLERS
STEP 11:
INSTALL
3” NIPPLES
STEP 8:
INSTALL
CORD GRIP