CONTROL PANEL OPERATING PROCEDURES
3-10
8. With the unit firing properly, it will be
controlled by the temperature controller
circuitry. The boiler’s
VALVE POSITION
will
be continuously displayed on the front panel
bargraph.
Once the demand for heat has been satisfied,
the Control Box will turn off the dual SSOV gas
valves. The blower relay will be deactivated and
the Air/Fuel Valve will be closed.
Standby
will
be displayed.
3.10 START/STOP LEVELS
The start and stop levels are the Air/Fuel Valve
positions (% open) that start and stop the unit,
based on load. These levels are Factory preset
as follows:
Start Level: 22%
Figure 3-6.
Air/Fuel Valve In Ignition Position
Stop Level: 18%
Normally, these settings should not require
adjustment.
6. Up to 7 seconds will be allowed for ignition
to be detected. The igniter relay will be
turned off one second after flame is
detected.
Note that the energy input of the boiler is not
linearly related to the Air/Fuel Valve position.
Refer to Table 3-7 on the following page for the
relationship between the energy input and valve
open position (%) for a unit running on natural
gas.
7. After 2 seconds of continuous flame,
Flame
Proven
will be displayed and the flame
strength will be indicated. After 5 seconds,
the current date and time will be displayed in
place of the flame strength.
Table 3-7.
Relationship Between Air/Fuel Valve Position and Energy Input For Unit Running On Natural Gas
Air/Fuel Valve Position
(% Open)
Energy Input
(BTU/Hr)
Boiler Energy Input
(% of Full Capacity)
0 0 0
10% 0 0
18%
(Stop Level)
100,000
5.0%
20% 202,000 10%
30% 428,000 21%
40% 705,000 35%
50% 956,000 48%
60% 1,390,000 70%
70% 1,770,000 89%
80% 1,890,000 95%
90% 1,960,000 98%
100% 2,000,000 100%
Summary of Contents for Benchmark 2.0
Page 4: ......
Page 8: ......
Page 12: ......
Page 24: ......
Page 44: ......
Page 50: ......
Page 78: ......
Page 84: ......
Page 88: ......
Page 90: ......
Page 101: ...APPENDIX F F 5 ...
Page 102: ...APPENDIX F F 6 ...
Page 104: ...APPENDIX F F 8 ...
Page 105: ...APPENDIX F F 9 ...
Page 106: ...APPENDIX F F 10 ...
Page 107: ...APPENDIX F F 11 ...
Page 108: ...APPENDIX F F 12 ...
Page 112: ...APPENDIX G G 4 ...
Page 113: ...APPENDIX H H 1 ...
Page 114: ...APPENDIX H H 2 ...
Page 115: ...APPENDIX H H 3 ...
Page 118: ......
Page 119: ...APPENDIX J BENCHMARK CONTROL PANEL EXPLODED VIEW J 1 ...
Page 120: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...
Page 122: ......