INITIAL START-UP
Combustion Oxygen Level at
45% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
7.2 %
<50 ppm
<30 ppm
40. If the oxygen level is not within the specified
range, adjust the level using the
▲
and
▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲
arrow key
increases the oxygen level and pressing the
▼
arrow key decreases the oxygen level.
41. Once the oxygen level is within the specified
range at 45%, press the
ENTER
key to store
the selected blower output voltage for the
45% valve position.
42. Press the
▲
arrow key until
SET Valve
Position
appears on the C-MORE display.
43. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
44. Press the
▼
arrow key until the
SET Valve
Position
reads
30%
, then press the
ENTER
key.
45. Press the
▼
arrow key until
CAL Voltage
30%
is displayed.
46. Press the
CHANGE
key.
CAL Voltage 30%
will begin to flash.
47. The oxygen level at the 30% valve position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
30% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
8.0 %
<50 ppm
<30 ppm
48. If the oxygen level is not within the specified
range, adjust the level using the
▲
and
▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲
arrow key
increases the oxygen level and pressing the
▼
arrow key decreases the oxygen level.
49. Once the oxygen level is within the specified
range at 30%, press the
ENTER
key to store
the selected blower output voltage for 30%
valve position.
50. Press the
▲
arrow key until
SET Valve
Position
appears on the C-MORE display.
51. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
52. Press the
▼
arrow key until the
SET Valve
Position
reads
16%
, then press the
ENTER
key.
53. Press the
▼
arrow key until
CAL Voltage
18%
is displayed.
54. Press the
CHANGE
key.
CAL Voltage 18%
will begin to flash.
55. The oxygen level at the 18% valve position
should be as shown below. Also, ensure that
the carbon monoxide (CO) and nitrogen
oxide (NOx) readings do not exceed the
values shown.
Combustion Oxygen Level at
18% Valve Position
Oxygen %
± 0.2
Carbon
Monoxide
NOx
8.0 %
<50 ppm
<30 ppm
56. If the oxygen level is not within the specified
range, adjust the level using the
▲
and
▼
arrow keys. This will adjust the output
voltage to the blower motor as indicated on
the display. Pressing the
▲
arrow key
increases the oxygen level and pressing the
▼
arrow key decreases the oxygen level.
57. Once the oxygen level is within the specified
range at 18%, press the
ENTER
key to store
the selected blower output voltage for 18%
valve position.
58. This completes the Natural Gas combustion
calibration procedure. Skip the Propane
Combustion Calibration procedure in
paragraph 4.4 and proceed directly to the
Proceed directly to the Unit Reassembly
procedure in paragraph 4.5.
4-5
Summary of Contents for Benchmark 2.0
Page 4: ......
Page 8: ......
Page 12: ......
Page 24: ......
Page 44: ......
Page 50: ......
Page 78: ......
Page 84: ......
Page 88: ......
Page 90: ......
Page 101: ...APPENDIX F F 5 ...
Page 102: ...APPENDIX F F 6 ...
Page 104: ...APPENDIX F F 8 ...
Page 105: ...APPENDIX F F 9 ...
Page 106: ...APPENDIX F F 10 ...
Page 107: ...APPENDIX F F 11 ...
Page 108: ...APPENDIX F F 12 ...
Page 112: ...APPENDIX G G 4 ...
Page 113: ...APPENDIX H H 1 ...
Page 114: ...APPENDIX H H 2 ...
Page 115: ...APPENDIX H H 3 ...
Page 118: ......
Page 119: ...APPENDIX J BENCHMARK CONTROL PANEL EXPLODED VIEW J 1 ...
Page 120: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...
Page 122: ......