TROUBLESHOOTING
TABLE 8-1. BOILER TROUBLESHOOTING – Continued
FAULT INDICATION
PROBABLE CAUSES
TROUBLESHOOTING/CORRECTIVE ACTION
LINE VOLTAGE
OUT OF PHASE
1. Line and Neutral switched in AC
Power Box.
2. Incorrect power supply transformer
wiring.
1. Check hot and neutral in AC Power Box to ensure they are not
reversed
2. Check transformer wiring, in AC Power Box, against the power
box transformer wiring diagram to ensure it is wired correctly
LOW GAS
PRESSURE
1. Incorrect supply gas pressure.
2. Defective Low Pressure Gas Switch
1. Measure gas pressure upstream of the supply gas regulator with
the unit firing. Refer to paragraph 2.7.1 to ensure that the gas
pressure is correct for the type of fuel and gas train being used.
2. Measure gas pressure at the low gas pressure switch. If it is
greater than 2.6” W.C. (or 2.1"W.C. for propane), measure
continuity across the switch and replace if necessary.
LOW WATER
LEVEL
1. Insufficient water level in system
2. Defective water level circuitry.
3. Defective water level probe.
1. Check system for sufficient water level.
2. Test water level circuitry using the Control Box front panel LOW
WATER TEST and RESET buttons. Replace water level
circuitry if it does not respond.
3. Check continuity of probe end to the shell, change probe if there
is no continuity.
MODBUS COMM
FAULT
1. Boiler not seeing information from
Modbus network
1. Check network connections. If fault persists, contact qualified
Service Personnel.
PRG SWTCH CLOSED
DURING IGNITION
1. A/F Valve rotated open to purge and
did not rotate to ignition position
2. Defective or shorted switch.
3. Switch wired incorrectly.
4. Defective Power Supply Board or
fuse
5. Defective IGST Board
1. Start the unit. The Air/Fuel Valve should rotate to the purge
(open) position, then back to ignition position (towards closed)
during the ignition cycle. If the valve does not rotate back to the
ignition position, check the Air/Fuel Valve calibration. If
calibration is okay, the problem may be in the Air/Fuel Valve or
the Control Box. Refer fault to qualified service personnel.
2. If the Air/Fuel Valve does rotate to the ignition position, check the
purge switch for continuity between the N.O. and COM terminals.
If the switch shows continuity when not in contact with the cam,
check to ensure that the switch is wired correctly (correct wire
numbers on the normally open terminals).
3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not
steady ON, replace Power Supply Board.
5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF
every second. If not, replace IGST Board.
8
-
8
Summary of Contents for Benchmark 2.0
Page 4: ......
Page 8: ......
Page 12: ......
Page 24: ......
Page 44: ......
Page 50: ......
Page 78: ......
Page 84: ......
Page 88: ......
Page 90: ......
Page 101: ...APPENDIX F F 5 ...
Page 102: ...APPENDIX F F 6 ...
Page 104: ...APPENDIX F F 8 ...
Page 105: ...APPENDIX F F 9 ...
Page 106: ...APPENDIX F F 10 ...
Page 107: ...APPENDIX F F 11 ...
Page 108: ...APPENDIX F F 12 ...
Page 112: ...APPENDIX G G 4 ...
Page 113: ...APPENDIX H H 1 ...
Page 114: ...APPENDIX H H 2 ...
Page 115: ...APPENDIX H H 3 ...
Page 118: ......
Page 119: ...APPENDIX J BENCHMARK CONTROL PANEL EXPLODED VIEW J 1 ...
Page 120: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...
Page 122: ......