BMK 750-3k Platinum Boiler OPERATION, SERVICE, and MAINTENANCE GUIDE
APPENDIX A: BOILER MENU DESCRIPTIONS
OMM-0116_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
95
of
178
GF-201
Ph.: 800-526-0288
03/15/2017
TABLE A-6: CALIBRATION MENU ITEM DESCRIPTIONS
See section 2-10 CALIBRATION Menu for a range of choices and the default values.
TABLE A-6: CALIBRATION MENU ITEM DESCRIPTIONS
MENU OPTION
DESCRIPTION
1
Stepper Fbk
Allows the Air/Fuel Valve stepper motor feedback current to be calibrated at
the 0% (fully closed) and 100% (fully open) positions. Verification can also
be accomplished at the 50% position.
2
Purge Timer
Allows adjustment of the pre-ignition purge time.
3
Post Purge Timer
Allows adjustment of the purge time when a unit shuts down.
4
IGN Position
Allows adjustment of the valve position (Fire Rate) during the ignition
sequence.
5
Ign Pos Hold Tmr
6
FFWD Temp Disply
Enabled or Disabled.
7
Outlet Tmp Dsply
Enabled or Disabled.
8
Inlet Tmp Dsply
Enabled or Disabled.
9
Valv Pos Out Dsp
Enabled or Disabled.
10
Exhaust Tmp Dsp
Enabled or Disabled.
11
Exhaust Safety
12
Flue Material
13
Exhst Fault Temp
14
Exhst Module Temp
15
Exhst Warn Temp
16
Exhst Tmp VP Adj
17
Exhst Adj Rate
18
VP Change Rate
19
VP Up Rate
Allows adjustment of the Valve Position (Fire Rate) increase rate when
raising the Valve Position. VP Up Rate is defined as Seconds per Step.
20
VP Down Rate
Allows adjustment of the Valve Position (Fire Rate) decrease rate when
lowering the Valve Position. VP Down Rate is defined as Seconds per Step.
21
Purge Blwr Offst
Allows adjustment of the blower speed (Blower Output Voltage) during the
Purge cycle.
22
4-20mA Purge Pct
Allows adjustment of the blower speed (Blower Output Voltage) during the
Purge cycle when using an Emerson VFD Drive to control the Blower Motor.
23
PWM In Adj
Allows the Pulse Width Modulation (PWM) duty cycle to be adjusted from -
5.0% to +5.0% in 0.1% increments.
24
Analog In Adj
Allows adjustment of the analog input from -5.0% to +5.0%.
25
Flow In Adj
Allows adjustment of the water Flow Rate Input from
-5.0% to +5.0%.