CONTROL PANEL OPERATING PROCEDURES
3.6 CONFIGURATION MENU
The Configuration Menu shown in Table 3-4
permits adjustment of the Internal Setpoint
(Setpt) temperature regardless of whether the
valid password has been entered. Setpt is
required for operation in the Constant Setpoint
mode. The remaining options in this menu
require the valid password to be entered, prior to
changing existing entries. This menu contains a
number of other configuration settings which
may or may not be displayed, depending on the
current operating mode setting.
NOTE
The Configuration Menu settings shown in
Table 3-4 are Factory-Set in accordance
with the requirements specified for each
individual order. Therefore, under normal
operating conditions, no changes will be
required.
Table 3-4. Configuration Menu
Available Choices or Limits
Menu Item Display
Minimum
Maximum
Default
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
Boiler or Water Heater
Boiler
Unit Size
0.5 MBTU, 1.0 MBTU
1.5 MBTU, 2.0 MBTU
2.5 MBTU, 3.0 MBTU
1.0 MBTU
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive
Combination
Outdoor Reset
Constant
Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (BMS)
Network
4 – 20 mA,
1-5V
Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F 230°F 70°F
Reset Ratio
(If Mode = Outdoor
Reset)
0.1 9.9 1.2
Outdoor Sensor
Enabled or Disabled
Disabled
System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F 100°F 60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
220°F
200°F
Temp Hi Limit
40°F
240°F
210°F
Max Fire Rate
40%
100%
100%
Pump Delay Timer
0 min.
30 min.
0 min.
Aux Start On Dly
0 sec.
120 sec.
0 sec.
3-6
Summary of Contents for GF-123
Page 4: ......
Page 8: ......
Page 36: ......
Page 42: ......
Page 68: ......
Page 76: ......
Page 78: ......
Page 84: ......
Page 89: ...APPENDIX F F 5 ...
Page 92: ...APPENDIX F F 8 ...
Page 94: ...APPENDIX F F 10 ...
Page 96: ...APPENDIX F F 12 ...
Page 100: ...APPENDIX G G 4 ...
Page 106: ......
Page 107: ...APPENDIX J BENCHMARK CONTROL PANEL EXPLODED VIEW J 1 ...
Page 108: ...APPENDIX J J 2 P1 P2 P3 P4 P5 P6 BENCHMARK CONTROL PANEL REAR VIEW ...