TF7038GB_A_NOT
7. MAINTENANCE AND SERVICE
EXTRAORDINARY MAINTENANCE
The Connect units are factory filled with R410A gas and fully tested. As per standard conditions, technical
service does not need to intervene to check the cooling gas. Over time, small losses may occur at the
joints causing the refrigerant to leak, draining the circuit. This will cause the unit to malfunction. In these
cases, the refrigerant outlet points must be determined, repaired and the cooling circuit replenished.
The following procedure should be used for filling:
•
Empty and drain the entire cooling circuit. Use a vacuum pump connected to both the low- and
high-pressure ports until the negative-pressure gauge reads approximately 10 Pa. Wait a few
minutes and make sure that said value does not rise above 50 Pa again.
•
Connect the cooling gas cylinder or filling cylinder to the connection on the low-pressure line.
•
Add the quantity of cooling gas specified on the unit type plate.
•
After a few hours of operation, check that the liquid indicator indicates that the circuit is dry (dry
–
green). In the case of partial losses, the circuit must be completely emptied before being refilled.
•
The refrigerant R410A may only be added when liquid.
•
Operating conditions that deviate from the nominal values lead to deviating values.
•
A leak test or leak detection may only be carried out with refrigerant R410A and suitable leak
detection devices.
•
The use of oxygen, acetylene or other flammable or toxic gases in the cooling circuit is prohibited,
as this can lead to explosions and poisoning.
CAUTION
Safety checks, maintenance work and repairs may only be carried out by a legally qualified
technician.
Inadequate inspections/maintenance work can lead to damage to objects and persons.
23