14 / 56
TF7128_A_NOT_INST_DXR230_EXC_MB
Aereco S.A.
3.4. DEFROSTING
The defrosting is located in the duct that serves the fresh air inlet, upstream from the DXR Unit. It is
therefore in Ø160 mm and insulated.
A length of 1 m must be respected between the DXR Unit
and the defrosting. The fresh air supply air duct must be manufactured from non-flammable
materials (A1 Class according to EN 13501-1).
The air must travel in the direction shown by the arrows marked on the
defrosting device.
325
250
Ø160 mm
View of the defrosting
Positioning of the defrosting compared to the
DXR Unit
The defrosting must be located at a distance of at least twice the connection diameter from a duct
bend or external grille, and at 1m from the DXR Unit. We recommend tilting the duct slightly towards
the exterior in order to keep rain water from getting into the defrosting.
The installation must allow access to the defrosting for a manual reset, or for maintenance
(access hatch).
Manual reset of the defrosting:
1. Unscrew the black cap
2. Push the red button and screw back the
black cap on
The defrosting must not be installed with the
electrical device at the bottom.
Note:
·The DXR Unit has been specially designed to work with the defrosting provided by Aereco (defrost
strategy specific to the DX System, and adapted diameter). Besides, it has been CEM certified with
the DXR Unit.
·Using another defrosting can lead to serious problems of functioning and degrade the security of
the system.
Anti-frost without pre-heating resistance
·When using the DXR Unit without the additional resistance pre-heating, the anti-frost strategy is
based on the supply airflow regulation. The supply air fan is switched off and the extract air fan
remains active, in order to warm up the heat exchanger.
Be careful, very often, this type of strategy does not comply with an open fireplace.
Make
sure that you comply with the standard in force in the country of installation.
When the optional defrosting device is used, this anti-frost strategy is not active anymore.
A 1200W preheater allows to warm 200 m
3
/h @ -20°C. If T° can fall down
bellow -20°C, 2 x 1200W preheaters may be implemented on the same
supply duct network. These 2 preheaters can be driven with only one 2I2O
module. In this situation, the amount power of the 2 preheaters is 2400W,
so this value has to be entered in the manufacturer access web page
(MAINTENANCE / MANUFACTURER ACCESS / Preheater power).
L > 1 m